Plan Review Notes
Plan Review Notes For Permit 15091208
Permit Number 15091208
Review Stop E
Sequence Number 1
Notes
Date Text
2015-10-21 20:32:40THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION
 OF THE FBC, (FLORIDA BUILDING CODE) 2014, AS APPLICABLE
 AND BELOW ARE THE DEFICIENCIES NOTED.
  
 1. YOU SHALL PROVIDE A DEDICATED SIGN OUTLET ADJACENT
 TO THE ?NEW IRON GATE?. NEC 600.5 REQUIRES THAT EVERY
 PEDESTRIAN ENTRY IN EVERY COMMERCIAL ESTABLISHMENT BE
 PROVIDED WITH PROVISIONS FOR SIGNAGE.
 2. YOU SHALL PROVIDE PROPER ILLUMINATION FOR THE AREA.
 3. YOU SHALL PROVIDE AN EMERGENCY/EXIT COMBINATION
 FIXTURE ABOVE THE NEW EXIT. THIS FIXTURE SHALL BE
 CONNECTED AHEAD OF ANY SWITCHING, ON THE SAME CIRCUIT
 PROVIDING THE REQUIRED LIGHTING FOR THE AREA IN
 QUESTION.
 4. PER NEC 310.15, YOU SHALL USE 3 # 3/0 CU CONDUCTORS
 FOR YOUR SERVICE FEEDERS.
 5. PER NEC 250.66, YOUR GROUNDING ELECTRODE CONDUCTOR
 SHALL BE NO LESS THAN A #4 CU.
 6. PER NEC 250.122, YOUR EQUIPMENT GROUND CONDUCTOR
 SHALL BE NO LESS THAN A #6 CU.
  
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE,
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  