| 2015-10-21 20:32:40 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION |
| | OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION |
| | OF THE FBC, (FLORIDA BUILDING CODE) 2014, AS APPLICABLE |
| | AND BELOW ARE THE DEFICIENCIES NOTED. |
| | |
| | 1. YOU SHALL PROVIDE A DEDICATED SIGN OUTLET ADJACENT |
| | TO THE ?NEW IRON GATE?. NEC 600.5 REQUIRES THAT EVERY |
| | PEDESTRIAN ENTRY IN EVERY COMMERCIAL ESTABLISHMENT BE |
| | PROVIDED WITH PROVISIONS FOR SIGNAGE. |
| | 2. YOU SHALL PROVIDE PROPER ILLUMINATION FOR THE AREA. |
| | 3. YOU SHALL PROVIDE AN EMERGENCY/EXIT COMBINATION |
| | FIXTURE ABOVE THE NEW EXIT. THIS FIXTURE SHALL BE |
| | CONNECTED AHEAD OF ANY SWITCHING, ON THE SAME CIRCUIT |
| | PROVIDING THE REQUIRED LIGHTING FOR THE AREA IN |
| | QUESTION. |
| | 4. PER NEC 310.15, YOU SHALL USE 3 # 3/0 CU CONDUCTORS |
| | FOR YOUR SERVICE FEEDERS. |
| | 5. PER NEC 250.66, YOUR GROUNDING ELECTRODE CONDUCTOR |
| | SHALL BE NO LESS THAN A #4 CU. |
| | 6. PER NEC 250.122, YOUR EQUIPMENT GROUND CONDUCTOR |
| | SHALL BE NO LESS THAN A #6 CU. |
| | |
| | THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN |
| | MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED |
| | FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED |
| | TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG |
| | WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE, |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY |
| | APPRECIATED. |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | |