2015-10-13 13:14:37BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15091208
 ADD: 427 NORTHWOOD AVE.
 CONT: OPEN SIGHTS CONSTRUCTION
 TEL: (786)246-7052
 E-MAIL: SACHAUZAN6GMAIL.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. OCT. 13/ 2015
 ACTION: DENIED
  
 1) PLEASE SUBMIT A FLOOR PLAN OF THE INTERIOR OF THE
 BUILDING. IN THE YEAR 1998-99 IT LOOKS LIKE THERE WERE
 PERMITS TO CONVERT THIS SPACE TO HAVE A COMMERCIAL
 KITCHEN. THERE WAS A PERMIT FOR A UNDER COUNTER GREASE
 TRAP. IT WOULD APPEAR THROUGH THE OCCUPATIONAL LISENCE
 THAT THE USE AS A CATERING BUSINESS THAT WOULD HAVE
 BEEN NO CHANGE OF OCCUPANCY. THE NEW OCCUPATIONAL
 LICESNE FOR TABLE 427 IS FOR A 43 SEAT RESTARAUNT. THIS
 MAY NOT BE A CHANGE OF OCCUPANCY BUT A CHANGE OF USE
 THAT WILL NEED TO BE REVIEWED BY ALL DISCIPLES FOR CODE
 COMPLIANCE. 2014 FBC-B 303.1.1. PLEASE NOTE THE
 OCCUPANT LOAD IS BASED ON THE SQUARE FOOTAGE OF THE
 BUILDING 15 SQ. FT PER OCCUPANT AND 200 SQUARE FEET PER
 OCCUPANT FOR COMMERCIAL KITCHENS.
  
 PLEASE NOTE THAT WE WILL ALSO NEED A FLOOR PLAN FOR THE
 ADDTIONAL OUSIDE SEASONAL SEATING. ONCE THE COMBINED
 OCCUPANT LOAD IS 50 OR GREATER THIS BECOMES A CHANGE OF
 OCCUPANCY AS WELL AS A CHANGE IN USE. CHAPTER 10 OF THE
 2014 EXISISTNG BUILDING CODE WOULD BE ENACTED. PLEASE
 NOTE THE NEW CONCRETE SLAB DEPICTED ON SHEET 3 IS
 APPROXIMATELY 1364 SQUARE FEET/ 15= 91 OCCUPANTS.
  
 2) SHEET # 3 SHOWS THE NEW OPENING INTO THE EXISITNG
 BUILDING WITH NEW VERTICAL STEEL ON EACH SIDE OF THE
 DOORWAY. THE PLANS SHOW THE VERTICAL REBAR TO THE
 LINTEL HEIGHT BUT GOING TO THE BEAM ABOVE THAT WILL
 MAKE THE VERTICAL REBAR PART OF THE MWFRS (MAIN WIND
 FORCE RESISTING SYSTEM).
  
 3A) NO PRODUCT APPROVAL WAS SUBMITTED FOR THE NEW DOOR
 OPENING. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 3B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 4) THE PRODUCT APPROVAL SUBMITTED FOR THE ACCORDIAN
 STORM SHUTTER DOES NOT HAVE ANY OF THE DETAILS
 HIGHLIGHTED (CIRCLED) FOR THE TOP AND BOTTOM TRACKS,
 SPANS, TYPE OF FASTENERS ETC. CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
  
 5) SHEET 1 AND 3 BOTH SHOW THE NEW GATES THAT EXIT TO
 THE STREET SWING IN. WHEN OCCUPANT LOADS GREATER THAN
 49 THEY NEED TO SWING IN THE DIRECTION OF TRAVEL. 2014
 FBC-B 1008.1.2.
  
 THE OTHER ISSUE WITH THE NEW GATES, WITH OUTSWING GATES
 THEY WILL NEED TO BE SET BACK SO THE OUTSWING GATES DO
 NOT SWING OUT OVER THE PROPERTY LINE. 2014 FBC-B
 3202.2.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  