Plan Review Notes
Plan Review Notes For Permit 15091201
Permit Number 15091201
Review Stop M
Sequence Number 1
Notes
Date Text
2015-10-23 07:30:081ST REVIEW: FBC 2010 MECHANICAL
 REVISION PERMIT #15091201
 MASTER PERMIT # 14050111
  
 1) THE SUBMITTED NARRATIVE FROM STEVEN FELLER P.E. DOES
 NOT LIST ALL THE CHANGES THAT ARE INDICATED ON THE
 PLANS. IF THE CHANGES WERE MADE UNDER PREVIOUS
 REVISIONS, PLEASE PLACE CLOUDS AND SYMBOLS ON THE PLANS
 FOR CLARIFICATION. PLEASE EXPAND THE NARRATIVE TO
 BRIEFLY EXPLAIN WHY SOME OF THESE CHANGES ARE BEING
 MADE. THE FOLLOWING LIST ARE "SOME" OF THE CHANGES I AM
 SEEING ON THE PLANS THAT ARE NOT IN THE NARRATIVE.
 A) SHEET M1.01: NEW VAV BOXES, VAV BOX RELOCATIONS,
 DUCTWORK CHANGES TO AC-3, AC-4, AC-5, DUCTWORK RUNS TO
 THE BALLROOM, MOTORIZED DAMPERS ADDED, LOUVER SIZE
 INCREASES, CHANGE TO RETURN AIR PLENUM, ETC.
 B) M1.02: RELOCATION OF AC-6 & AC-7, NEW INSTALLATION
 OF FIRE-RATED SUPPLY AND RETURN GRILLS AT THE DOCK
 OFFICE, AND RECONFIGURING OF DUCTWORK FOR ALL AC
 SYSTEMS, ETC. PROVIDE SUBMITTALS FOR THE FIRE-RATED
 GRILLS.
 C) M1.03: RELOCATION OF AC-13, VAV BOX RELOCATIONS,
 DUCTWORKWORK CHANGES, ETC.
 D) M1.04: RELOCATION OF AC-15, CHANGES TO THE RETURN
 AIR SYSTEMS IN THE MEETING ROOMS, ETC.
 E) M1.05: CHANGE IN RETURN AIR PLENUM, CHANGES TO RETUN
 AIR DUCTING TO AC-4, ETC.
 F) M1.09- M1.12: PLEASE CLARIFY WHY THE FIRE DAMPERS AT
 THE ELEVATOR LOBBIES WERE CHANGED TO FIRE/SMOKE
 DAMPERS.
 G) M2.0: CLARIFY WHY THE HP WAS EXCLUDED FROM THE EXEC.
 LOUNGE.
 H) M4.1: CLARIFY WHY HP-6, 7, & 8 WERE ADDED TO THE
 SCHEDULE AND WHERE ARE THEY LOCATED ON THE PLANS.
 PROVIDED SIZING CALCULATIONS FOR THE UNITS PER SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION.
 I) M4.2: CLARIFY WHY THE STAIR PRESSURIZATION FANS WERE
 CHANGED AND REDUCED IN CFM CAPACITY, AND WHY SPF-1 WAS
 CHANGED FROM "UTILITY" TO "MIXED FLOW". PROVIDE
 SUBMITTALS FOR THE NEW FANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER