Plan Review Notes
Plan Review Notes For Permit 15091199
Permit Number 15091199
Review Stop E
Sequence Number 1
Notes
Date Text
2015-10-14 11:07:09PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE
 ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
 1. NFPA 72, SECTION 17.14.6 REQUIRES THAT THE MANUAL
 PULL STATION DEVICES BE LOCATION NO MORE THAN 5? FROM
 THE EXITS IN THE PATH OF EGRESS.
 2. THE LOWER LOBBY AS INDICATED ON THE DRAWINGS IS
 MISSING MANUAL INITIATION DEVICES, (PULL STATIONS).
 3. IF THE REASON FOR THE PLACEMENT OF THESE DEVICES SO
 DISTANT FROM THE DOOR WAY IS DUE TO GLASS FACADE,
 PLEASE NOTE THAT THE CODE DOES NOT MAKE AN EXCEPTION
 FOR THIS.
 4. THOUGH THE ADDITION OF THE MISSING PULL STATIONS
 WILL NOT ALTER THE CALCS, THEY WILL ALTER RISER
 DIAGRAM.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  