Plan Review Notes
Plan Review Notes For Permit 15091190
Permit Number 15091190
Review Stop B
Sequence Number 2
Notes
Date Text
2015-10-23 17:07:25PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE CALCULATIONS AND PLANS ARE REQUIRED TO HAVE THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE ON THEM
 (FACSIMILES ARE NOT ACCEPTABLE). FAC 61G15-23.002
  
 2) THE DESIGN CALCULATIONS ARE FOR MOUNTING SIGNS TO
 MASONRY WALLS AND THE WALLS THE SIGNS WILL BE MOUNTED
 ON FOR THIS PROJECT ARE WIRE LATH AND STUCCO ON PLYWOOD
 ATTACHED TO METAL FRAMING. THE ANCHOR SPACING OF THE
 PAIRS OF ANCHORS AT 40 INCHES ON CENTER IS MORE THAN
 THE 19 INCHES ON CENTER THAT IS SPECIFIED IN THE ANCHOR
 SCHEDULE FOR THE 1/2" PLYWOOD WALL MATERIAL ON THE SIGN
 DRAWINGS. FBC 3107.1 & 1604.1
  
 3) THE PLANS ARE TOO SMALL AND WILL BE AN ISSUE FOR THE
 FIELD INSPECTORS, AS WELL AS, FOR RECORD KEEPING
 PURPOSES. THE INFORMATION IN THE ANCHOR SCHEDULE
 REQUIRES MAGNIFICATION IN ORDER TO BE READ. FBC
 107.2.1.4
  
 4) THE ENGINEER'S SEAL IS REQUIRED TO BE A MINIMUM OF
 1-7/8 INCHES IN DIAMETER PER FAC 61G15-23.001. THE SEAL
 ON THE SIGN DRAWINGS DOES NOT COMPLY.