| Plan Review Notes For Permit 15091186 |
| Permit Number |
15091186 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-02 17:16:07 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15091186 | | | 10/3/15 | | | | | | 1) THE SUBMITTED CUT SHEET FOR THE REPLACEMENT FAN | | | INFDICATES IT WAS CERTIFIED BY PAUL WRIGHT FOR HVAC | | | ASSOCIATES INC. THE TWO PARTIES LISTED ARE OBVIOUSLY | | | NOT CONNECTED WITH THIS PROJECT. PLEASE REMOVE THE | | | SUBMITTAL FROM THE PERMIT FILE. | | | 2) SIZING AND SELECTION OF THE REPLACEMENT | | | PRESSURIZATION FAN SHALL BE DONE BY A FL. LICENSED | | | ENGINEER. PROVIDE A SUBMITTAL FOR THE PROPOSED FAN WITH | | | THE ENGINEER OF RECORD'S REVIEW AND APPROVAL SIGNATURE | | | ON THE DOCUMENT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|