| Plan Review Notes For Permit 15091145 |
| Permit Number |
15091145 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-11-13 17:37:39 | 2ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL | | | | | | THE PLAN HAS CONFLICTS IN THAT IT CITES THE 2008 NEC | | | AND THE 2011 NEC. NEITHER APPLY AS THE CODE IN EFFECT | | | IS REFERENCED ABOVE AND ELECTRICAL REQUIREMENTS ARE | | | CONTAINED THEREIN IN PART VIII - ELECTRICAL. | | | | | | PROVIDE THE FOLLOWING MINIMUM PLAN REVIEW INFORMATION: | | | | | | FBC- 107.3.5.3 ELECTRIC SERVICE RISER WITH WIRE SIZES, | | | CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE LOAD | | | CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON | | | FLOOR PLAN. | | | | | | THIS IS AN INCOMPLETE REVIEW BASED UPON AN INADEQUATE | | | SUBMITTAL. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|