| 2015-10-21 18:16:50 | 1ST REVIEW: FBC 2014 5TH ED. | | | | | | THIS PROJECT IS A RENOVATION AS DEFINED IN THE FBC | | | ENERGY VOLUME THEREFORE PROVIDE THE FOLLOWING: | | | | | | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 | | | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO | | | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. | | | | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW | | | SUPPLY DUCTS PER FBC-R M16 & BATH EXHAUST PER FBC-R | | | M15. | | | FBC-ER403.6.1 PROVIDE AN EQUIPMENT SIZING CALCULATION | | | | | | THIS IS AN INCOMPLETE REVIEW BASED ON INSUFFICIENT | | | DETAIL PROVIDED. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|