| 2015-10-21 18:22:20 | 1ST REVIEW: FBC 2014 5TH ED. | | | | | | FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE | | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE | | | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON | | | FLOOR PLAN. | | | | | | THIS IS AN INCOMPLETE REVIEW BASED UPON AN INADEQUATE | | | SUBMITTAL. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|