| Plan Review Notes For Permit 15091010 |
| Permit Number |
15091010 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-30 16:23:22 | 600 OKEECHOBEE BOULEVARD | | | PERMIT #15091010 | | | MASTER #14050111 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | IS ONLY THE DOOR STATUS BEING MONITORED OR ARE THERE | | | TRULY A SECURE AND UNSECURE SIDES ON THE DOORS?THE | | | DETAILED SECTION VIEWS INDICATE A SECURE AND UNSECURE | | | SIDE OF THE DOOR. WHAT METHOD IS BEING UTILIZED TO GAIN | | | ENTRY FROM THE SECURE SIDE..CARD READERS? NOTHING IS | | | INDICATED ON THE PLANS. | | | | | | IF THE DOORS HAVE A SECURED SIDE, SEVERAL DOORS AFFECT | | | THE ARCHITECT'S LIFE SAFETY EGRESS PLAN BY CREATING | | | DEAD-END CORRIDORS AND RESTRICTED EGRESS. FOR EXAMPLE, | | | THE DOOR ADJACENT TO STAIR #2 IN SERVICE CORRIDOR #127 | | | WILL CREATE A DEAD-END CORRIDOR IF THE DOOR IS SECURED | | | FROM THE CORRIDOR SIDE. THE SAME CONDITION EXISTS IN | | | CORRIDOR #103B. THE MEETING ROOMS ON THE 2ND FLOOR ARE | | | REQUIRED TO HAVE FREE EGRESS INTO THE ROOMS FROM THE | | | CORRIDOR TO BYPASS THE "CONVENIENCE OPENING." THESE ARE | | | ONLY A COUPLE EXAMPLES. COORDINATION IS NEEDED BETWEEN | | | THE SECURITY PLANS AND LIFE SAFETY PLANS. | | | | | | NOTE: SECURITY DEVICES AND/OR WIRING WILL NOT BE | | | PERMITTED WITHIN THE FIRE RATED STAIR ENCLOSURES. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|