2015-09-26 04:21:281) SUBMIT TWO COPIES OF THE FUEL DISPENSER
 MANUFACTURER'S INSTALLATION INSTRUCTIONS PER NFPA 58,
 2011 EDITION, SEC. 6.24.3.1.
 2) NFPA 58 SEC. 6.24.3.6 - PIPING AND THE DISPENSING
 HOSE SHALL BE PROVIDED WITH HYDROSTATIC RELIEF VALVES
 IN ACCORDANCE WITH SECTION 6.13 OF NFPA 58.
 3) NFPA 58-2011 - SEC. 6.24.3.7 - PROTECTION AGAINST
 TRESPASSING AND TAMPERING SHALL BE IN ACCORDANCE WITH
 6.18.4. SHOW ON THE PLAN HOW THE TANKS WILL BE
 PROTECTED AGAINST UNAUTHORIZED ACCESS.
 4) NFPA 58-2011 - SEC. 6.24.3.12 - ALL DISPENSERS
 EITHER SHALL BE INSTALLED ON A CONCRETE FOUNDATION OR
 SHALL BE PART OF A COMPLETE STORAGE AND DISPENSING UNIT
 MOUNTED ON A COMMON BASE AND INSTALLED IN ACCORDANCE
 WITH 6.6.3.1 (G). SHOW COMPLIANCE WITH TABLE 6.6.3 (A).
 5) PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE PER
 THE WPB AMEND. TO FBC SEC. 107.2.1.4.
  