2015-10-22 15:40:51THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION
 OF THE FBC, (FLORIDA BUILDING CODE) 2014, AS APPLICABLE
 AND BELOW ARE THE DEFICIENCIES NOTED.
 1. THERE IS NO ELECTRICAL INFORMATION ACCOMPANYING THIS
 SUBMITTAL FOR A REVIEW.
 2. PLEASE PROVIDE DETAILED INFORMATION ON THE PROPOSED
 WORK.
 3. I WILL NEED A COMPLETE SITE SPECIFIC RISER DIAGRAM
 INCLUDING ALL GROUNDING AND CONDUCTOR SIZING.
 4. YOU SHALL SUBMIT A PANEL SCHEDULE WITH RESPECTIVE
 LOAD CALCS.
 5. INDICATE THE LOCATION OF ALL MAIN DISCONNECTS.
 6. AL EQUIPMENT SHALL HAVE THE ARC-FLASH WARNING
 LABELS.
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE,
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  