| 2015-09-26 03:11:20 | 1) SUBMIT 2 COPIES OF A ROOF PLAN (CAN BE HAND DRAWN) | | | THAT SHOWS THE LOCATION OF THE SCUPPERS, GUTTERS | | | (INCLUDE GUTTER DIMENSIONS) AND DOWNSPOUTS. WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | 2) SUBMIT INFORMATION AS TO HOW THE SIZING OF THE | | | SCUPPERS, DOWNSPOUTS AND GUTTERS WAS ATTAINED. SHOW THE | | | SQUARE FOOTAGE AREA OF THE ROOF DRAINED BY THE GUTTERS, | | | SCUPPERS AND DOWNSPOUTS.COMPLY WITH 2014 FBC-PLUMBING, | | | SEC.1106.6, 1106.7. | | | 3) INDICATE ON THE PLAN WHERE THE DOWNSPOUTS TERMINATE. | | | DOWNSPOUTS SHALL TERMINATE A MINIMUM OF 1 FOOT FROM THE | | | BUILDING SIDEWALL PER 2014 FBC SEC.1503.7. | | | 4) THE SIZING SHALL BE DONE BASED ON A 5 INCH PER HOUR | | | RAINFALL RATE PER FIGURE 1106.1 OF 2014 FBC-PLUMBING. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|