Plan Review Notes
Plan Review Notes For Permit 15090991
Permit Number 15090991
Review Stop P
Sequence Number 1
Notes
Date Text
2015-09-26 03:11:201) SUBMIT 2 COPIES OF A ROOF PLAN (CAN BE HAND DRAWN)
 THAT SHOWS THE LOCATION OF THE SCUPPERS, GUTTERS
 (INCLUDE GUTTER DIMENSIONS) AND DOWNSPOUTS. WPB AMEND.
 TO FBC SEC. 107.2.1.
 2) SUBMIT INFORMATION AS TO HOW THE SIZING OF THE
 SCUPPERS, DOWNSPOUTS AND GUTTERS WAS ATTAINED. SHOW THE
 SQUARE FOOTAGE AREA OF THE ROOF DRAINED BY THE GUTTERS,
 SCUPPERS AND DOWNSPOUTS.COMPLY WITH 2014 FBC-PLUMBING,
 SEC.1106.6, 1106.7.
 3) INDICATE ON THE PLAN WHERE THE DOWNSPOUTS TERMINATE.
 DOWNSPOUTS SHALL TERMINATE A MINIMUM OF 1 FOOT FROM THE
 BUILDING SIDEWALL PER 2014 FBC SEC.1503.7.
 4) THE SIZING SHALL BE DONE BASED ON A 5 INCH PER HOUR
 RAINFALL RATE PER FIGURE 1106.1 OF 2014 FBC-PLUMBING.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  