Plan Review Notes
Plan Review Notes For Permit 15090984
Permit Number 15090984
Review Stop G
Sequence Number 2
Notes
Date Text
2016-01-07 08:42:301) THE MINIMUM SIZE OF THE GAS LINE TO THE COOKTOP
 SHALL BE 3/4" PER 2014 FBCR TABLE G2413.4 (1). THE GAS
 RISER SHOWS THE DROP TO THE COOKTOP AS 3/4" BUT IT IS
 BEING SUPPLIED BY A 1/2" LINE. THE ENTIRE LINE TO THE
 COOKTOP HAS TO BE 3/4", NOT JUST A SECTION OF IT. 2ND
 REQUEST.
 2) SCH. 40 GALVANIZED CANNOT BE USED BELOW GROUND PER
 2014 FBCR SEC. G2415.11, G2415.11.1, G2415.11.2. THE
 NOTE IS STILL ON THE PLAN.INDICATE ON THE PLAN THE TYPE
 OF PIPE MATERIAL TO BE USED BELOW GROUND. WPB AMEND. TO
 FBC SEC. 107.2.1.2ND REQUEST.
 3) SHOW THE SIZES OF ALL OF THE EXISTING GAS PIPING.
 WITH THE ADDED TANKLESS WATER HEATER, THE EXISTING GAS
 PIPING MAY BE UNDERSIZED AND MAY HAVE TO BE INCREASED.
 THE MINIMUM SIZE GAS SUPPLY LINE SUPPLYING 248,000
 BTU'S AT PRESSURE BELOW 2 PSI PER TABLE G2413.4 (1) OF
 THE 2014 FBCR SHALL BE 1 1/4" FOR THE DISTANCE SHOWN ON
 THE PLANS.
 4) SOME CORRECTIONS WERE MADE TO ONLY ONE COPY OF THE
 PLANS. PLEASE MAKE CORRECTIONS TO BOTH SETS OF PLANS.
 5) VENTING SHALL BE IN ACCORDANCE WITH THE 2014 FUEL
 GAS CODE, NOT THE 2010. REVISE NOTE ON THE PLAN.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  