| Plan Review Notes For Permit 15090984 |
| Permit Number |
15090984 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-01-07 08:42:30 | 1) THE MINIMUM SIZE OF THE GAS LINE TO THE COOKTOP | | | SHALL BE 3/4" PER 2014 FBCR TABLE G2413.4 (1). THE GAS | | | RISER SHOWS THE DROP TO THE COOKTOP AS 3/4" BUT IT IS | | | BEING SUPPLIED BY A 1/2" LINE. THE ENTIRE LINE TO THE | | | COOKTOP HAS TO BE 3/4", NOT JUST A SECTION OF IT. 2ND | | | REQUEST. | | | 2) SCH. 40 GALVANIZED CANNOT BE USED BELOW GROUND PER | | | 2014 FBCR SEC. G2415.11, G2415.11.1, G2415.11.2. THE | | | NOTE IS STILL ON THE PLAN.INDICATE ON THE PLAN THE TYPE | | | OF PIPE MATERIAL TO BE USED BELOW GROUND. WPB AMEND. TO | | | FBC SEC. 107.2.1.2ND REQUEST. | | | 3) SHOW THE SIZES OF ALL OF THE EXISTING GAS PIPING. | | | WITH THE ADDED TANKLESS WATER HEATER, THE EXISTING GAS | | | PIPING MAY BE UNDERSIZED AND MAY HAVE TO BE INCREASED. | | | THE MINIMUM SIZE GAS SUPPLY LINE SUPPLYING 248,000 | | | BTU'S AT PRESSURE BELOW 2 PSI PER TABLE G2413.4 (1) OF | | | THE 2014 FBCR SHALL BE 1 1/4" FOR THE DISTANCE SHOWN ON | | | THE PLANS. | | | 4) SOME CORRECTIONS WERE MADE TO ONLY ONE COPY OF THE | | | PLANS. PLEASE MAKE CORRECTIONS TO BOTH SETS OF PLANS. | | | 5) VENTING SHALL BE IN ACCORDANCE WITH THE 2014 FUEL | | | GAS CODE, NOT THE 2010. REVISE NOTE ON THE PLAN. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|