| 2016-01-19 15:02:35 | PLAN REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT TWO COPIES OF A SURVEY OF THE PROPERTY. FBC |
| | 107.2.1 |
| | |
| | 2) SUBMIT TWO SETS OF ENERGY COMPLIANCE FORMS FOR THE |
| | ADDITION. SHOW COMPLIANCE WITH 2014 FBC ENERGY |
| | CONSERVATION SECT. R101.4.3 & R103.2 BY SUBMITTING THE |
| | PROPER CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING |
| | FORMS 402 OR 405. (THE FORMS ARE REQUIRED TO BE SIGNED |
| | AND DATED BY THE OWNER/AGENT.) |
| | |
| | 3) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED |
| | TO INSTALL THE CONCRETE ROOF TILE AND RESIST THE |
| | REQUIRED OVERTURN MOMENT. THIS CAN BE ACCOMPLISHED BY |
| | CIRCLING THE APPROPRIATE METHOD ON THE PRODUCT |
| | APPROVAL. IF A ROOF TILE ADHESIVE WILL BE USED, SUBMIT |
| | TWO SETS OF THE PRODUCT APPROVALS FOR IT. |
| | |
| | 4) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE |
| | WINDOWS, DOORS AND ROOFING MATERIALS THAT HAVE BEEN |
| | APPROVED BY THE HISTORIC PLANNER AND HAVE BEEN REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. DCA |
| | RULE 9N-3 AND FBC 107.3.4.1 |
| | |
| | 5) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ARCHED |
| | TOP DOORS THAT HAVE BEEN REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD. DCA RULE 9N-3 AND |
| | FBC 107.3.4.1 |
| | |
| | 6) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE SINGLE |
| | HUNG WINDOWS THAT HAVE BEEN REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD. DCA RULE 9N-3 AND |
| | FBC 107.3.4.1 |
| | |
| | 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |