2016-01-19 15:02:35PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO COPIES OF A SURVEY OF THE PROPERTY. FBC
 107.2.1
  
 2) SUBMIT TWO SETS OF ENERGY COMPLIANCE FORMS FOR THE
 ADDITION. SHOW COMPLIANCE WITH 2014 FBC ENERGY
 CONSERVATION SECT. R101.4.3 & R103.2 BY SUBMITTING THE
 PROPER CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING
 FORMS 402 OR 405. (THE FORMS ARE REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER/AGENT.)
  
 3) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE CONCRETE ROOF TILE AND RESIST THE
 REQUIRED OVERTURN MOMENT. THIS CAN BE ACCOMPLISHED BY
 CIRCLING THE APPROPRIATE METHOD ON THE PRODUCT
 APPROVAL. IF A ROOF TILE ADHESIVE WILL BE USED, SUBMIT
 TWO SETS OF THE PRODUCT APPROVALS FOR IT.
  
 4) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 WINDOWS, DOORS AND ROOFING MATERIALS THAT HAVE BEEN
 APPROVED BY THE HISTORIC PLANNER AND HAVE BEEN REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. DCA
 RULE 9N-3 AND FBC 107.3.4.1
  
 5) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ARCHED
 TOP DOORS THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. DCA RULE 9N-3 AND
 FBC 107.3.4.1
  
 6) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE SINGLE
 HUNG WINDOWS THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. DCA RULE 9N-3 AND
 FBC 107.3.4.1
  
 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  