| 2015-10-04 08:27:17 | 1) THE MINIMUM SIZE OF THE GAS LINE TO THE COOKTOP | | | SHALL BE 3/4" PER 2014 FBCR TABLE G2413.4 (1). | | | 2) SCH. 40 GALVANIZED CANNOT BE USED BELOW GROUND PER | | | 2014 FBCR SEC. G2415.11, G2415.11.1, G2415.11.2. | | | 3) GAS APPLIANCES SHALL BE LISTED AND LABELED.2014 FBCR | | | G2404.3. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|