2015-10-30 11:48:50PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHEET S-3 OF THE PLANS HAS SEVERAL REFERENCES TO THE
 2010 FBC. THE FBC FIFTH EDITION (2014) WENT INTO EFFECT
 ON JUNE 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR
 AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE FBC FIFTH EDITION. THE 2011 NEC IS THE
 CORRECT EDITION AND THE 2008 NEC IS SPECIFIED ON SHEET
 A-1.0.
  
 2) SUBMIT TWO COPIES OF A SURVEY OF THE PROPERTY. FBC
 107.2.1
  
 3) A SEPARATE PERMIT, APPLICATION AND REVIEW IS
 REQUIRED FOR THE WALL AND GATE RELOCATION.
  
 4) A SEPARATE PERMIT, APPLICATION AND REVIEW IS
 REQUIRED FOR THE CANVAS AWNINGS.
  
 5) SUBMIT TWO SETS OF ENERGY COMPLIANCE FORMS FOR THE
 ADDITION. SHOW COMPLIANCE WITH 2014 FBC ENERGY
 CONSERVATION SECT. R101.4.3 & R103.2 BY SUBMITTING THE
 PROPER CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING
 FORMS 402 OR 405.
  
 6) DETAIL 3 ON SHEET A4.1 APPEARS TO SHOW ROOF TILE ON
 FLAT ROOF AREAS, WHICH IS NOT ALLOWED BY THE BUILDING
 CODE. THE MINIMUM SLOPE FOR CONCRETE OR CLAY ROOF TILE
 IS 2:12 PER FBC-R905.3.2.
  
 7) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE ON
 SHEET S-3. FBC-R301.2.1
  
 8) THE ROOF AND WALL PRESSURES ON SHEET S-3 APPEAR TO
 BE INCORRECT FOR A STRUCTURE LOCATED IN EXPOSURE C WITH
 A 132 MPH VASD WIND SPEED. SPECIFY THE ROOF SLOPE FOR
 THE ROOF COMPONENT AND CLADDING PRESSURE TABLE ON THE
 PLANS. FBC-R301.2.1
  
 9) ON SHEET S-2 THE LOWER ROOF FRAMING PLAN THERE ARE
 TAGS WITH C/S3 AND D/S3. THERE ARE NO DETAILS ON SHEET
 S3 THAT ARE LABELED C OR D.
  
 10) THERE APPEARS TO BE SOME ERRORS IN THE TAGS ON THE
 PARTIAL UPPER ROOF FRAMING ON SHEET S-2. THERE IS ONE
 WITH 786 OVER A 1 RATHER THAN THE LETTER A. THERE IS
 ONE WITH A D OVER 270 AND AN 8 OVER 270. THESE LAST TWO
 APPEAR TO HAVE THE UPLIFT AND CONNECTOR REVERSED.
 PLEASE CLARIFY.
  
 11) SUBMIT TWO SETS OF MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR THE CARLISLE WATERPROOFING SYSTEM. FBC
 107.2.1.3
  
 12) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE CONCRETE ROOF TILE AND RESIST THE
 REQUIRED OVERTURN MOMENT. THIS CAN BE ACCOMPLISHED BY
 CIRCLING THE APPROPRIATE METHOD ON THE PRODUCT
 APPROVAL. IF A ROOF TILE ADHESIVE WILL BE USED, SUBMIT
 TWO SETS OF THE PRODUCT APPROVALS FOR IT.
  
 13) THE PVC - VINYL WIDOWS AND DOORS, WHOSE PRODUCT
 APPROVALS WERE SUBMITTED, ARE NOT APPROVED TO BE USED
 IN THIS PROJECT BY THE HISTORIC PLANNER. SUBMIT TWO
 SETS OF PRODUCT APPROVALS FOR THE WINDOWS AND DOORS
 THAT HAVE BEEN APPROVED BY THE HISTORIC PLANNER AND
 HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. FBC 107.3.4.1
  
 14) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ARCHED
 TOP WOOD ENTRY DOOR THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. FBC
 107.3.4.1
  
 15) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  