| 2015-10-30 11:48:50 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SHEET S-3 OF THE PLANS HAS SEVERAL REFERENCES TO THE |
| | 2010 FBC. THE FBC FIFTH EDITION (2014) WENT INTO EFFECT |
| | ON JUNE 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR |
| | AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND |
| | REFERENCE THE FBC FIFTH EDITION. THE 2011 NEC IS THE |
| | CORRECT EDITION AND THE 2008 NEC IS SPECIFIED ON SHEET |
| | A-1.0. |
| | |
| | 2) SUBMIT TWO COPIES OF A SURVEY OF THE PROPERTY. FBC |
| | 107.2.1 |
| | |
| | 3) A SEPARATE PERMIT, APPLICATION AND REVIEW IS |
| | REQUIRED FOR THE WALL AND GATE RELOCATION. |
| | |
| | 4) A SEPARATE PERMIT, APPLICATION AND REVIEW IS |
| | REQUIRED FOR THE CANVAS AWNINGS. |
| | |
| | 5) SUBMIT TWO SETS OF ENERGY COMPLIANCE FORMS FOR THE |
| | ADDITION. SHOW COMPLIANCE WITH 2014 FBC ENERGY |
| | CONSERVATION SECT. R101.4.3 & R103.2 BY SUBMITTING THE |
| | PROPER CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING |
| | FORMS 402 OR 405. |
| | |
| | 6) DETAIL 3 ON SHEET A4.1 APPEARS TO SHOW ROOF TILE ON |
| | FLAT ROOF AREAS, WHICH IS NOT ALLOWED BY THE BUILDING |
| | CODE. THE MINIMUM SLOPE FOR CONCRETE OR CLAY ROOF TILE |
| | IS 2:12 PER FBC-R905.3.2. |
| | |
| | 7) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE ON |
| | SHEET S-3. FBC-R301.2.1 |
| | |
| | 8) THE ROOF AND WALL PRESSURES ON SHEET S-3 APPEAR TO |
| | BE INCORRECT FOR A STRUCTURE LOCATED IN EXPOSURE C WITH |
| | A 132 MPH VASD WIND SPEED. SPECIFY THE ROOF SLOPE FOR |
| | THE ROOF COMPONENT AND CLADDING PRESSURE TABLE ON THE |
| | PLANS. FBC-R301.2.1 |
| | |
| | 9) ON SHEET S-2 THE LOWER ROOF FRAMING PLAN THERE ARE |
| | TAGS WITH C/S3 AND D/S3. THERE ARE NO DETAILS ON SHEET |
| | S3 THAT ARE LABELED C OR D. |
| | |
| | 10) THERE APPEARS TO BE SOME ERRORS IN THE TAGS ON THE |
| | PARTIAL UPPER ROOF FRAMING ON SHEET S-2. THERE IS ONE |
| | WITH 786 OVER A 1 RATHER THAN THE LETTER A. THERE IS |
| | ONE WITH A D OVER 270 AND AN 8 OVER 270. THESE LAST TWO |
| | APPEAR TO HAVE THE UPLIFT AND CONNECTOR REVERSED. |
| | PLEASE CLARIFY. |
| | |
| | 11) SUBMIT TWO SETS OF MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS FOR THE CARLISLE WATERPROOFING SYSTEM. FBC |
| | 107.2.1.3 |
| | |
| | 12) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED |
| | TO INSTALL THE CONCRETE ROOF TILE AND RESIST THE |
| | REQUIRED OVERTURN MOMENT. THIS CAN BE ACCOMPLISHED BY |
| | CIRCLING THE APPROPRIATE METHOD ON THE PRODUCT |
| | APPROVAL. IF A ROOF TILE ADHESIVE WILL BE USED, SUBMIT |
| | TWO SETS OF THE PRODUCT APPROVALS FOR IT. |
| | |
| | 13) THE PVC - VINYL WIDOWS AND DOORS, WHOSE PRODUCT |
| | APPROVALS WERE SUBMITTED, ARE NOT APPROVED TO BE USED |
| | IN THIS PROJECT BY THE HISTORIC PLANNER. SUBMIT TWO |
| | SETS OF PRODUCT APPROVALS FOR THE WINDOWS AND DOORS |
| | THAT HAVE BEEN APPROVED BY THE HISTORIC PLANNER AND |
| | HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. FBC 107.3.4.1 |
| | |
| | 14) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ARCHED |
| | TOP WOOD ENTRY DOOR THAT HAVE BEEN REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD. FBC |
| | 107.3.4.1 |
| | |
| | 15) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |