Plan Review Notes For Permit 15090967
Permit Number 15090967
Review Stop E
Sequence Number 3
Notes
Date Text
2016-01-22 10:22:29YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED
 DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL
 REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED
 BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO
 SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE
 REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION
 OF ANY PREVIOUS COMMENTS. THESE PLANS HAVE BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE) AND THE FBC, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS IN EFFECT AT THE TIME OF SUBMITTAL.
  
 1. ALL EXTERIOR LIGHTING SHALL COMPLY WITH FBC?E
 SECTIONS C405.6.1 & C405.6.2
  
 TO THIS COMMENT YOU PROVIDED A PHOTOMETRIC PLAN, BUT
 FAIL TO INCLUDE THE POWER DENSITY ALLOWANCE CHART
 SHOWING COMPLIANCE.
  
 2. PROVIDE WIRING DETAIL OR CALCULATIONS INDICATING
 COMPLIANCE WITH FBC?E405.7.3
  
 YOU DID PROVIDE A RISER DIAGRAM AS REQUIRED, BUT DO NOT
 INDICATE ON THE RISER DIAGRAM DETAIL OR ON THE
 ELECTRICAL PLAN ANY PROTECTION FOR THIS EQUIPMENT. NEC
 110.27(B) REQUIRES THAT THERE BE PROTECTION FROM
 PHYSICAL DAMAGE FOR THIS EQUIPMENT. FURTHERMORE, YOUR
 RISER DIAGRAM CONFLICTS WITH ?ELECTRICAL GENERAL NOTES?
 #2 WHICH PROHIBIT THE USE OF ALUMINUM CONDUCTORS.
  
 3. YOU SHALL PROVIDE A FIXTURE SCHEDULE AND AN
 ABBREVIATION AND SYMBOLS LEGEND
  
 THE FIXTURE SCHEDULE SAID TO BE ON SHEET GE1 IS
 MISSING. THE FIXTURE SCHEDULE SHALL BE ON THE PLAN SET.
  
 4. UNLESS PRIOR ARRANGEMENTS ARE MADE WITH THE
 ELECTRICAL INSPECTOR, ALL TRENCHING SHALL REMAIN OPEN
 FOR INSPECTION. NO SITE TUBES ARE ALLOWED.
  
 FOR FULL COMPLIANCE WITH THIS, PLEASE INCLUDE A NOTE ON
 THE PLANS STATING THAT TRENCHES WILL REMAIN OPEN UNTIL
 INSPECTED.
  
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE
 NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  