2015-12-17 16:57:11THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. ALL EXTERIOR LIGHTING SHALL COMPLY WITH FBC-E
 SECTIONS C405.6.1 & C405.6.2
 2. PROVIDE WIRING DETAIL OR CALCULATIONS INDICATING
 COMPLIANCE WITH FBC-E405.7.3
 3. YOU SHALL PROVIDE A FIXTURE SCHEDULE AND AN
 ABBREVIATION AND SYMBOLS LEGEND
 4. UNLESS PRIOR ARRANGEMENTS ARE MADE WITH THE
 ELECTRICAL INSPECTOR, ALL TRENCHING SHALL REMAIN OPEN
 FOR INSPECTION. NO SITE TUBES ARE ALLOWED.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  