| 2015-12-17 16:57:11 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1. ALL EXTERIOR LIGHTING SHALL COMPLY WITH FBC-E |
| | SECTIONS C405.6.1 & C405.6.2 |
| | 2. PROVIDE WIRING DETAIL OR CALCULATIONS INDICATING |
| | COMPLIANCE WITH FBC-E405.7.3 |
| | 3. YOU SHALL PROVIDE A FIXTURE SCHEDULE AND AN |
| | ABBREVIATION AND SYMBOLS LEGEND |
| | 4. UNLESS PRIOR ARRANGEMENTS ARE MADE WITH THE |
| | ELECTRICAL INSPECTOR, ALL TRENCHING SHALL REMAIN OPEN |
| | FOR INSPECTION. NO SITE TUBES ARE ALLOWED. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |