Plan Review Notes
Plan Review Notes For Permit 15090967
Permit Number 15090967
Review Stop E
Sequence Number 1
Notes
Date Text
2015-10-08 12:32:14I INITIALLY STAMPED THE DRAWINGS FOR THE SITE LIGHTING
 ELECTRIC, BUT HAD TO FAIL THE APPLICATION DUE TO
 INCOMPLETE SUBMITTAL. YOU SHALL PROVIDE SPECS ON THE
 PROPOSED LUMINARIES AND SUPPORTING POLES AS WELL AS FOR
 THE GATE OPENERS AND READERS. YOU SHALL ALSO INCLUDE A
 DETAIL ON THE MOUNTING AND GROUNDING OF THE POLES. THE
 APPLICATION ALSO MENTIONED CAR CHARGERS AND NO MENTION
 OF CAR CHARGERS APPEARS ON THE PANELS NOR IS THE
 REQUIRED LITERATURE FOR THE CHARGERS INCLUDED. A BLDG
 STOP WILL BE ADDED.