2015-11-23 14:17:082ND REVIEW 2014 MECHANICAL
 PERMIT #15090952
 11/23/15
  
 1) SHEET M2.1: THERE IS A FIRE/SMOKE DAMPER MISSING
 WHERE THE 32X20 DUCT PENETRATES THE MECHANICAL ROOM
 FIRE-RATED WALL. PLEASE PROVIDE A SYMBOL AT THE
 LOCATION, AND SUBMIT A PRODUCT SPEC SHEET REVIEWED AND
 APPROVED BY THE ENGINEER OF RECORD.
  