| Plan Review Notes For Permit 15090952 |
| Permit Number |
15090952 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-11-23 14:17:08 | 2ND REVIEW 2014 MECHANICAL | | | PERMIT #15090952 | | | 11/23/15 | | | | | | 1) SHEET M2.1: THERE IS A FIRE/SMOKE DAMPER MISSING | | | WHERE THE 32X20 DUCT PENETRATES THE MECHANICAL ROOM | | | FIRE-RATED WALL. PLEASE PROVIDE A SYMBOL AT THE | | | LOCATION, AND SUBMIT A PRODUCT SPEC SHEET REVIEWED AND | | | APPROVED BY THE ENGINEER OF RECORD. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|