Plan Review Notes
Plan Review Notes For Permit 15090952
Permit Number 15090952
Review Stop M
Sequence Number 1
Notes
Date Text
2015-10-02 09:12:591ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090952
 10/3/15
  
 1) SHEET M2.1, KEY NOTE #8: PLEASE CLARIFY IF THE
 ADJACENT CORRIDOR WALL IS FIRE-RATED, AND INDICATE THE
 EXACT LOCATION OF THE DAMPER ACCESS DOOR. PLEASE NOTE
 THE WINDLOCK ACCESS PANEL PER MANUFACTURER SPECS IS
 NON-RATED.
 2) M4.1: PLEASE REVIEW AND UPDATE THE ASHRAE 62.1
 REFERENCE TO 2010 PER THE FBC-14 MECHANICAL CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  