| Notes |
| Date |
Text |
| 2015-10-02 09:12:59 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15090952 | | | 10/3/15 | | | | | | 1) SHEET M2.1, KEY NOTE #8: PLEASE CLARIFY IF THE | | | ADJACENT CORRIDOR WALL IS FIRE-RATED, AND INDICATE THE | | | EXACT LOCATION OF THE DAMPER ACCESS DOOR. PLEASE NOTE | | | THE WINDLOCK ACCESS PANEL PER MANUFACTURER SPECS IS | | | NON-RATED. | | | 2) M4.1: PLEASE REVIEW AND UPDATE THE ASHRAE 62.1 | | | REFERENCE TO 2010 PER THE FBC-14 MECHANICAL CODE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|