2015-11-09 10:33:25THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION
 OF THE 2014 FBC, (FLORIDA BUILDING CODE) AS APPLICABLE
 AND BELOW ARE THE DEFICIENCIES NOTED.
  
 1. NEC 215.5. YOU SHALL SUBMIT ACCURATE & SITE SPECIFIC
 FEEDER DIAGRAM SHOWING DETAILS OF CONDUCTOR SIZING AND
 LOADS.
 2. NEC 220.16. YOU SHALL PROVIDE ACCURATE LOADS CALCS.
 AS MENTIONED.
 3. NEC 408.4(B). ALL PANEL BOARDS SHALL BE MARKED TO
 INDICATE THE LOCATION OF THEIR POWER SOURCE.
 4. NEC 110.16. PROVIDE ARC-FLASH HAZARD WARNING LABELS
 ON ALL PANELBOARDS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  