| 2015-11-03 13:15:53 | |
| | ****NOTE: |
| | THIS REVIEW MAY BE APPROVED WITH PROVISO IF CONTRACTOR |
| | AGREES. FEES MAY APPLY. CONTACT JULIO GOMEZ FOR MORE |
| | INFORMATION. |
| | |
| | |
| | RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- REVISE EQUIPMENT SIZING CALCULATIONS SUBMITTED: |
| | A) THE FRONT DOOR DOESN'T FACE SOUTH. SEE PLANS AND |
| | REVISE AS REQUIRED. SEC. R403.6.1 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | B) CALCULATIONS TO MATCH REVISED PLANS. SEE COMMENT |
| | #2(A) BELOW. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | C) THERE IS NOT CRAWL SPACE. SEE PLANS. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | 2- A/C PLAN SUBMITTED: |
| | A) A/C PLAN DOESN'T MATCH ARCHITECTURAL PLANS. REVISE |
| | AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | B) CLEARLY IDENTIFY ALL ROOMS ON THE SECOND FLOOR PLAN. |
| | THE ROOMS ARE UNLABELED. NEED COMPLETE INFORMATION FOR |
| | PROPER REVIEW. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | C) PROVIDE THE NAME AND SIGNATURE FOR THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | D) EQUIPMENT LISTED EXCEEDS THE EQUIPMENT SIZING |
| | CALCULATIONS. SEC. R403.6.1 OF FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE INSERT ANY REVISED DRAWINGS AND REMOVE OLD |
| | DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |