Plan Review Notes
Plan Review Notes For Permit 15090946
Permit Number 15090946
Review Stop B
Sequence Number 1
Notes
Date Text
2015-11-02 12:36:11 
  
 ****NOTE:
 THIS BUILDING REVIEW MAY BE APPROVED WITH PROVISO IF
 CONTRACTOR AGREES. FEES MAY APPLY. CONTACT JULIO GOMEZ
 FOR MORE INFORMATION.
  
  
  
 RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE; FBC 5TH EDITION (2014).
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- CLEARLY SPECIFY SIZE AND TYPE OF EXISTING WINDOWS TO
 BE REPLACED AND TYPE AND SIZE OF PROPOSED WINDOWS TO
 VERIFY COMPLIANCE WITH THE BEDROOM EGRESS REQUIREMENTS
 AS REQUIRED BY SEC. 704 OF FBC-EXISTING BUILDING, 5TH
 EDITION (2014).
  
 3- SPECIFY CARBON MONOXIDE ALARM WITHIN 10 FEET OF EACH
 SLEEPING ROOM AS REQUIRED BY SEC. R315 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 SPECIFY LOCATION OF CARBON MONOXIDE ALARMS IN PLANS.
  
 4- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS.
  
 5- SHEET A.04:
 A) CLARIFY DOOR AND WINDOW SCHEDULE. THERE IS MORE THAN
 ONE DOOR AND WINDOW WITH THE SAME MARK AND DIFFERENT
 SIZES. FOR EXAMPLE DO5, WO1, WO2, ETC. REVISE AS
 REQUIRED AND COORDINATE WITH ITEM #2 ABOVE. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B) REVISE STUCCO THICKNESS. TABLE R702.1(1) OF
 FBC-RESIDENTIAL, 5TH EDITION (2014) REQUIRES 7/8" MIN.
 THICKNESS.
  
 6- SHEET S-1:
 A) ACCORDING TO SEC. R301.2.1.4.1 AND SEC. R301.2.1.4.3
 FBC-RESIDENTIAL, 5TH EDITION (2014) THIS PROPERTY IS
 LOCATED IN EXPOSURE "D" NOT "C". REVISE WINDOW
 PRESSURES AS REQUIRED. ALSO, REVISE BASIS OF DESIGN ON
 SHEET S-2 TO REFLECT THE CORRECT EXPOSURE.
  
 B) PROVIDE THE DESIGN PRESSURES FOR DOORS ALSO. SEC.
 R301 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 7- REVISE ENERGY CALCULATIONS (NOTE: THIS HOUSE IS A
 CONTRIBUTING HISTORIC HOUSE. ENERGY CALCULATIONS ARE
 NOT REQUIRED, BUT IF SUBMITTING THEM, THEN REVISE AS
 SPECIFIED BELOW):
 A) THIS IS NOT NEW CONSTRUCTION. SEE PLANS AND REVISE
 ITEM #1. SEC. R101.5.1.1.2 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 B) FLOOR TYPE DOESN'T MATCH PLANS. WHERE IS THE
 CRAWLSPACE?. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) ROOF INFORMATION ON PAGE 2 OF 5. REVISE MATERIAL
 SPECIFIED TO MATCH PLANS AND WHERE IS THE GABLE AREA?.
 SEC. R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 D) REVISE WINDOWS OVERHANG SEPARATION TO MATCH PLANS.
 SEC. R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 E) A/C EQUIPMENT LISTED EXCEEDS THE SIZE REQUIRED BY
 THE EQUIPMENT SIZING CALCULATIONS. SEC. R403.6.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 F) PROVIDE THE NAME OF THE BUILDER ON TOP OF THE FORM.
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING
 THE DEFAULT FACTOR FOR GLAZING.
  
 8- SOIL TEST REPORT SUBMITTED:
 A) ENGINEER OF RECORD SPECIFIES 2500 PSF SOIL BEARING
 CAPACITY ON SHEET S-2. SOIL TEST REPORT SPECIFIED
 ACHIEVEMENT OF 2000 PSF SOIL BEARING CAPACITY. ENGINEER
 OF RECORD TO ADDRESS THIS ISSUE AND REVISE DESIGN
 SPECIFICATIONS AS REQUIRED. SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) SOIL TEST REPORT TO HAVE ENGINEER'S ORIGINAL SEAL
 AND SIGNATURE AS REQUIRED BY CHAPTER 471 F.S.
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF
 RECORD. SEE TILE NOA FOR LISTED ADHESIVES.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 LIST THE FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE
 SPECIFIED CONNECTOR.
  
 10- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS. PLEASE PLACE REVIEW STAMP ON FRONT OF THE
 PAGE NOT ON THE BACK OF THE PAGE. THIS IS FOR RECORD
 KEEPING PURPOSES.
  
 11- FIXED WINDOWS, SINGLE HUNG WINDOWS, WINDOW
 MULLIONS, FRENCH DOORS NOA'S SUBMITTED: CLEARLY
 IDENTIFY SIZE AND TYPE TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE ENGINEER'S CALCULATED DESIGN
 PRESSURES FOR EXPOSURE "D". SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 12- CLEARLY IDENTIFY ALL ROOMS ON THE SECOND FLOOR
 PLAN. THERE ARE SOME ROOMS THAT ARE UNLABELED. NEED
 COMPLETE INFORMATION FOR PROPER REVIEW. SEC. 107.2.1
 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EWACH
 COMMETN TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWINGS AND REMOVE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]