2016-03-17 14:13:174TH REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090929
 3/17/16
  
 1) THE RE-SUBMITTED M100 PLAN FROM GM CONSULTING
 ENGINEERS IS INDICATING THE BOILER FLUE IS A B-VENT
 TYPE FOR A CATEGORY 1 APPLIANCE, HOWEVER THE NEWLY
 SUBMITTED MANUFACTURER'S SPECIFCATIONS FROM VAN PACKER
 FOR THE BOILER SPECIFI A FORCED DRAFT VENTING SYSTEM .
 PLEASE SEE THE DEFINITIONS OF CATEGORY-1, TYPE B VENT,
 AND FORCED DRAFT IN SECTION 202 FBC-14 FUEL GAS:
  
 A) CATEGORY I. AN APPLIANCE THAT OPERATES WITH A
 NONPOSITIVE VENT STATIC PRESSURE AND WITH A VENT GAS
 TEMPERATURE THAT AVOIDS EXCESSIVE CONDENSATE PRODUCTION
 IN THE VENT.
 B) TYPE B VENT. A VENT LISTED AND LABELED FOR USE WITH
 APPLIANCES WITH DRAFT HOODS AND OTHER CATEGORY I
 APPLIANCES THAT ARE LISTED FOR USE WITH TYPE B VENTS.
 C) FORCED-DRAFT VENTING SYSTEM. A PORTION OF A VENTING
 SYSTEM USING A FAN OR OTHER MECHANICAL MEANS TO CAUSE
 THE REMOVAL OF FLUE OR VENT GASES UNDER POSITIVE STATIC
 VENT PRESSURE.
 IT WOULD APPEAR THAT THE M100 PLAN INDICATING A
 CATEGORY 1 APPLIANCE WITH A TYPE B VENT IS NOT
 CONSISTENT WITH THE MANUFACTURER'S SPECIFICATIONS FROM
 VAN-PACKER.
 2) PLEASE PROVIDE AN UPDATED WIND LOAD ENGINEERING
 SUBMITTAL FOR INSTALLATION OF THE FLUE ABOVE THE ROOF.
 THE PLAN IN THE FILE HAS BEEN MARKED VOID BY EITHER THE
 CONTRACTOR OR DESIGN PROFESSIONAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  