| Plan Review Notes For Permit 15090929 |
| Permit Number |
15090929 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-02-05 10:45:13 | 1) ALL THE PLANS AND SUPPORTING DOCUMENTS SHALL BE | | | COMPILED INTO TWO COMPLETE SETS OF PLANS FOR | | | SUBMITTAL.2014 FBC SEC. 107.2.1. | | | 2) THE PLANS FROM GM CONSULTING ENGINEERS SHOWS THE | | | BOILER EXHAUST BEING VENTED WITH 2- 45 DEGREE OFFSETS | | | BUT THE PLANS FROM RIZA ALTAN SHOWS THE SAME VENT WITH | | | 2- 90 DEGREE FITTINGS. CLARIFY. | | | 3) THE PLUMBING RISER FROM TURQUOISE ENGINEERING SHOWS | | | 3-FLOOR SINKS, A VENT AND A FLOOR DRAIN FOR THIS | | | INSTALLATION. ONLY 2 FLOOR SINKS ARE SHOWN ON THE PLAN | | | BY GM CONSULTING ENGINEERS. A TRAP PRIMER IS REQUIRED | | | ON THE FLOOR DRAIN.CLARIFY.2014 FPC SEC.1002.4 | | | 4) THE 8 1/2" X 11 SHEET FROM BONDTECH IS ILLEGIBLE. | | | SUBMIT A CLEAR AND LEGIBLE SHEET FOR REVIEW.FBC SEC. | | | 107.2.1. | | | 5) A BACKFLOW PREVENTER (RPZ) IS REQUIRED ON THE WATER | | | FEED TO THE BOILER. 2014 FPC SEC. 608.3. | | | 6) |
|