Plan Review Notes
Plan Review Notes For Permit 15090929
Permit Number 15090929
Review Stop P
Sequence Number 3
Notes
Date Text
2016-02-05 10:45:131) ALL THE PLANS AND SUPPORTING DOCUMENTS SHALL BE
 COMPILED INTO TWO COMPLETE SETS OF PLANS FOR
 SUBMITTAL.2014 FBC SEC. 107.2.1.
 2) THE PLANS FROM GM CONSULTING ENGINEERS SHOWS THE
 BOILER EXHAUST BEING VENTED WITH 2- 45 DEGREE OFFSETS
 BUT THE PLANS FROM RIZA ALTAN SHOWS THE SAME VENT WITH
 2- 90 DEGREE FITTINGS. CLARIFY.
 3) THE PLUMBING RISER FROM TURQUOISE ENGINEERING SHOWS
 3-FLOOR SINKS, A VENT AND A FLOOR DRAIN FOR THIS
 INSTALLATION. ONLY 2 FLOOR SINKS ARE SHOWN ON THE PLAN
 BY GM CONSULTING ENGINEERS. A TRAP PRIMER IS REQUIRED
 ON THE FLOOR DRAIN.CLARIFY.2014 FPC SEC.1002.4
 4) THE 8 1/2" X 11 SHEET FROM BONDTECH IS ILLEGIBLE.
 SUBMIT A CLEAR AND LEGIBLE SHEET FOR REVIEW.FBC SEC.
 107.2.1.
 5) A BACKFLOW PREVENTER (RPZ) IS REQUIRED ON THE WATER
 FEED TO THE BOILER. 2014 FPC SEC. 608.3.
 6)