Plan Review Notes
Plan Review Notes For Permit 15090929
Permit Number 15090929
Review Stop M
Sequence Number 3
Notes
Date Text
2016-02-03 07:30:533RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090929
 2/3/15
  
 1) AFTER TWO PREVIOUS REVIEW REQUESTS, THE REVISED M100
 BOILER FLUE INSTALLATION DETAIL IS STILL NOT SHOWING A
 TOTAL RUN LENGTH OF THE VENT WHICH IS REQUIRED TO
 VERIFY CORRECT SIZING DAIMETER OF THE VENT. THE DRAWING
 IS "NTS" BUT BY APPEARANCES THE 12" DIAMETER VENT MAY
 BE UNDERSIZED FOR THE TOTAL LENGTH OF THE RUN. REFER TO
 TABLE 504.2(1) FBC-14 FUEL GAS AND REVISE THE PLAN TO
 SHOW THE TOTAL RUN LENGTH AND CORRECT VENT SIZING PER
 THE TABLE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER