Plan Review Notes
Plan Review Notes For Permit 15090929
Permit Number 15090929
Review Stop G
Sequence Number 3
Notes
Date Text
2016-03-18 13:02:241) SHT. M-100 INDICATES A TYPE "B" VENT FOR THE
 BOILER.THE GAS CODE REFERS TO CATEGORY I APPLIANCES
 BEING USED WITH A TYPE B VENT AND THESE TYPE OF
 APPLIANCES OPERATE UNDER A NONPOSITIVE VENT STATIC
 PRESURE. THE REPORT FROM VAN-PACKER INDICATES THAT THE
 BOILER IS A FORCED DRAFT SYSTEM AND THEREFORE CANNOT BE
 USED WITH A TYPE B VENT.
 2) PLEASE COMPILE THE PLANS INTO TWO COMPLETE SETS OF
 PLANS FOR REVIEW.
 3) THE 12" VENT IS UNDERSIZED FOR THE BOILER IN
 ACCORDANCE WITH TABLE 504.2 (1) OF 2014 FUEL GAS CODE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR