| Plan Review Notes For Permit 15090929 |
| Permit Number |
15090929 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-03-18 13:02:24 | 1) SHT. M-100 INDICATES A TYPE "B" VENT FOR THE | | | BOILER.THE GAS CODE REFERS TO CATEGORY I APPLIANCES | | | BEING USED WITH A TYPE B VENT AND THESE TYPE OF | | | APPLIANCES OPERATE UNDER A NONPOSITIVE VENT STATIC | | | PRESURE. THE REPORT FROM VAN-PACKER INDICATES THAT THE | | | BOILER IS A FORCED DRAFT SYSTEM AND THEREFORE CANNOT BE | | | USED WITH A TYPE B VENT. | | | 2) PLEASE COMPILE THE PLANS INTO TWO COMPLETE SETS OF | | | PLANS FOR REVIEW. | | | 3) THE 12" VENT IS UNDERSIZED FOR THE BOILER IN | | | ACCORDANCE WITH TABLE 504.2 (1) OF 2014 FUEL GAS CODE. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|