| Date |
Text |
| 2015-12-20 07:41:21 | 1) WATER ABOVE 140 DEGRESS SHALL NOT BE DISCHARGED INTO |
| | ANY PART OF A DRAINAGE SYSTEM PER 2014 FBC-PLUMBING |
| | SEC. 803.1. |
| | 2) SHT. P100 - IDENTIFY AND SIZE THE DRAIN FROM THE |
| | FEEDWATER TANK TO THE FLOOR SINK. WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 3) SHT. P-200 - THE MINIMUM AIR GAP REQD. FOR THE |
| | INDIRECT WASTE PIPES SHALL BE NOT LESS THE TWICE THE |
| | EFFECTIVE OPENING OF THE INDIRECT WASTE PIPE. 2014 FBC |
| | PLUMBING SEC.802.2.1. |
| | 4) SHT. P-200 - SHOW THE WATER SUPPLY TO THE AUTOCLAVE |
| | BLOWDOWN TANK ON THE AUTOCLAVE INSTALLATION DETAIL |
| | DRAWING.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 5) SHT. P-200 - THE PTR VALVE FOR THE AUTOCLAVE SHALL |
| | DISCHARGE BY GRAVITY PER 2014 FMC SEC.1006.5. |
| | 6) SUBMIT AN INSTALLATION DETAIL FOR THE AUTOCLAVE |
| | BLOWDOWN TANK TO THE AUTOCLAVE. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 7) SHT. P-200 SHOWS THE FLOOR SINKS AS EXISTING BUT |
| | SHT. 1 DOES NOT. ARE THEY NEW OR EXISTING? CLARIFY. |
| | 8) THE FLOOR DRAINS ARE NOT VENTED. SHOW THE PROPER |
| | VENTING FOR THE FLOOR FRAINS. FBC-PLUMBING SEC.901.2, |
| | 901.2.1. THE DISTANCE OF THE TRAP TO A VENT SHALL |
| | COMPLY WITH TABLE 909.1. |
| | 9) TRAP PRIMERS ARE REQD. ON THE FLOOR DRAINS PER |
| | FBC-PLUMBING SEC.1002.4. |
| | 10) THE 8 1/2 X 11 SHEET FROM BONDTECH IS ILLEGIBLE. |
| | SUBMIT A CLEAR AND LEGIBLE SHEET FOR REVIEW. WPB AMEND. |
| | TO FBC SEC.107.2.1. |
| | 11) THE BOILER SHALL BE LISTED IN ACCORDANCE WITH THE |
| | 2014 FL. MECHANICAL CODE SEC.1004.1. |
| | 12) SUBMIT COMPLETE SPCIFICATIONS FOR THE FEEDWATER |
| | TANK AND THE BOILER. WPB AMEND. TO FBC SEC.107.2.1. |
| | 130 INDICATE ON THE PLAN THE TYPE OF PIPING TO BE USED |
| | FOR THE STEAM SYSTEM. WPB AMEND. TO FBC SEC.107.2.1. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |