2015-12-18 16:03:021ST REVIEW 2014 MECHANICAL
 PERMIT #15090929
 12/18/15
  
 THE1ST REVIEW COMMENTS # 1 & 2 WERE NOT ADDRESSED. I AM
 NOT SEEING ANY DIMENSIONS INDICATING THE DIAMETER OF
 THE DUCT AND THE LENGTH OF THE DUCT RUN- SEE TABLE
 504.2(1) FBC-14 FUEL GAS. I HAVE COPIED COMMENTS #1 & 2
 BELOW: PLEASE REVISE THE PLANS TO INDICATE COMPLIANCE.
 1) WORKING CLEARANCE- REFER TO SECTION 1004.3 FBC-014
 MECHANICAL: "PASSAGEWAYS AROUND ALL SIDES OF BOILERS
 SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 18"
 UNLESS OTHERWISE APPROVED". THE SUBMITTED FLOOR PLAN
 DRAWING INDICATES NON-COMPLIANCE- PLEASE REVISE.
 2) PROVIDE DETAILS FOR EXHAUST VENTING OF THE BOILER:
 SHOW THE TYPE AND SIZE OF EXHAUST VENT, EXHAUST VENT
 RUN AND TERMINATION LOCATION, AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS.
 3) PLEASE PROVIDE A TIE-DOWN DETAIL FOR ANCHORING THE
 EXHAUST VENT ASSEMBLY ABOVE THE ROOF TO THE ROOF
 STRUCTURE.
 4) SUBMIT TWO COPIES OF THE MIAMI-DADE NOA FOR THE
 COMBUSTION AIR LOUVERS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER