| 2015-12-18 16:03:02 | 1ST REVIEW 2014 MECHANICAL | | | PERMIT #15090929 | | | 12/18/15 | | | | | | THE1ST REVIEW COMMENTS # 1 & 2 WERE NOT ADDRESSED. I AM | | | NOT SEEING ANY DIMENSIONS INDICATING THE DIAMETER OF | | | THE DUCT AND THE LENGTH OF THE DUCT RUN- SEE TABLE | | | 504.2(1) FBC-14 FUEL GAS. I HAVE COPIED COMMENTS #1 & 2 | | | BELOW: PLEASE REVISE THE PLANS TO INDICATE COMPLIANCE. | | | 1) WORKING CLEARANCE- REFER TO SECTION 1004.3 FBC-014 | | | MECHANICAL: "PASSAGEWAYS AROUND ALL SIDES OF BOILERS | | | SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 18" | | | UNLESS OTHERWISE APPROVED". THE SUBMITTED FLOOR PLAN | | | DRAWING INDICATES NON-COMPLIANCE- PLEASE REVISE. | | | 2) PROVIDE DETAILS FOR EXHAUST VENTING OF THE BOILER: | | | SHOW THE TYPE AND SIZE OF EXHAUST VENT, EXHAUST VENT | | | RUN AND TERMINATION LOCATION, AND SUBMIT MANUFACTURER'S | | | SPECIFICATIONS. | | | 3) PLEASE PROVIDE A TIE-DOWN DETAIL FOR ANCHORING THE | | | EXHAUST VENT ASSEMBLY ABOVE THE ROOF TO THE ROOF | | | STRUCTURE. | | | 4) SUBMIT TWO COPIES OF THE MIAMI-DADE NOA FOR THE | | | COMBUSTION AIR LOUVERS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|