| Plan Review Notes For Permit 15090929 |
| Permit Number |
15090929 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-04 07:05:00 | 1) THE FLOOR DRAINS ARE NOT VENTED. SHOW THE PROPER | | | VENTING FOR THE FLOOR FRAINS. FBC-PLUMBING SEC.901.2, | | | 901.2.1. THE DISTANCE OF THE TRAP TO A VENT SHALL | | | COMPLY WITH TABLE 909.1. | | | 2) TRAP PRIMERS ARE REQD. ON THE FLOOR DRAINS PER | | | FBC-PLUMBING SEC.1002.4. | | | 3) THE 8 1/2 X 11 SHEET FROM BONDTECH IS ILLEGIBLE. | | | SUBMIT A CLEAR AND LEGIBLE SHEET FOR REVIEW. WPB AMEND. | | | TO FBC SEC.107.2.1. | | | 4) THE BOILER SHALL BE LISTED IN ACCORDANCE WITH THE | | | 2014 FL. MECHANICAL CODE SEC.1004.1. | | | 5) SPECIFICATIONS HAVE BEEN SUBMITTED FOR THE BOILER | | | BUT NO PIPING DIAGRAM HAS BEEN SUBMITTED. INDICATE ON | | | THE PLAN THAT THE BOILER INSTALLATION WILL BE DONE | | | UNDER A SEPARATE PERMIT IF NOT BEING DONE AT THIS | | | TIME.IF IT IS, SUBMIT COMPLETE PIPING DIAGRAM FOR | | | REVIEW. WPB AMEND. TO FBC SEC.107.2.1. | | | 6) SUBMIT COMPLETE SPCIFICATIONS FOR THE FEEDWATER TANK | | | AND SUBMIT THE COVER SHEET FOR THE BOILER. WPB AMEND. | | | TO FBC SEC.107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|