2015-10-04 07:05:001) THE FLOOR DRAINS ARE NOT VENTED. SHOW THE PROPER
 VENTING FOR THE FLOOR FRAINS. FBC-PLUMBING SEC.901.2,
 901.2.1. THE DISTANCE OF THE TRAP TO A VENT SHALL
 COMPLY WITH TABLE 909.1.
 2) TRAP PRIMERS ARE REQD. ON THE FLOOR DRAINS PER
 FBC-PLUMBING SEC.1002.4.
 3) THE 8 1/2 X 11 SHEET FROM BONDTECH IS ILLEGIBLE.
 SUBMIT A CLEAR AND LEGIBLE SHEET FOR REVIEW. WPB AMEND.
 TO FBC SEC.107.2.1.
 4) THE BOILER SHALL BE LISTED IN ACCORDANCE WITH THE
 2014 FL. MECHANICAL CODE SEC.1004.1.
 5) SPECIFICATIONS HAVE BEEN SUBMITTED FOR THE BOILER
 BUT NO PIPING DIAGRAM HAS BEEN SUBMITTED. INDICATE ON
 THE PLAN THAT THE BOILER INSTALLATION WILL BE DONE
 UNDER A SEPARATE PERMIT IF NOT BEING DONE AT THIS
 TIME.IF IT IS, SUBMIT COMPLETE PIPING DIAGRAM FOR
 REVIEW. WPB AMEND. TO FBC SEC.107.2.1.
 6) SUBMIT COMPLETE SPCIFICATIONS FOR THE FEEDWATER TANK
 AND SUBMIT THE COVER SHEET FOR THE BOILER. WPB AMEND.
 TO FBC SEC.107.2.1.
  
 PLUMBING PLAN REVIEW