2015-10-07 08:26:591ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090929
 10/7/15
  
 1) WORKING CLEARANCE- REFER TO SECTION 1004.3 FBC-014
 MECHANICAL: "PASSAGEWAYS AROUND ALL SIDES OF BOILERS
 SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 18"
 UNLESS OTHERWISE APPROVED". THE SUBMITTED FLOOR PLAN
 DRAWING INDICATES NON-COMPLIANCE- PLEASE REVISE.
 2) PROVIDE DETAILS FOR EXHAUST VENTING OF THE BOILER:
 SHOW THE TYPE AND SIZE OF EXHAUST VENT, EXHAUST VENT
 RUN AND TERMINATION LOCATION, AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS.
 3) REFER TO SECTION 1006.6- SAFETY AND RELIEF VALVE
 DISCHARGE: "HIGH PRESSURE-STEAM SAFETY VALVES SHALL BE
 VENTED TO THE OUTSIDE OF THE STRUCTURE" PLEASE PROVIDE
 DETAILS.
 4) REFER TO SECTION 1008.1 AND INDICATE COMPLIANCE FOR
 THE REQUIRED BLOWOFF VALVE AND BLOWOFF VALVE DISCHARGE
 LOCATION.
 5) PROVIDE PIPING DIAGRAMS OR SCHEMATICS FOR THE BOILER
 AND OTHER EQUIPMENT ASSOCIATED WITH THE SYSTEM.
 INDICATE THE TYPES AND SIZES OF ALL PIPING, VALVE TYPES
 AND LOCATIONS ETC.
 6) PROVIDE UL TESTED AND APPROVED FIRESTOPPING DETAILS
 FOR ALL PIPES AND DUCTS PENETRATING THE FIRE-RATED
 BOILER ENCLOSURE AND THE ROOF STRUCTURE.
  