| 2015-10-07 08:26:59 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15090929 | | | 10/7/15 | | | | | | 1) WORKING CLEARANCE- REFER TO SECTION 1004.3 FBC-014 | | | MECHANICAL: "PASSAGEWAYS AROUND ALL SIDES OF BOILERS | | | SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 18" | | | UNLESS OTHERWISE APPROVED". THE SUBMITTED FLOOR PLAN | | | DRAWING INDICATES NON-COMPLIANCE- PLEASE REVISE. | | | 2) PROVIDE DETAILS FOR EXHAUST VENTING OF THE BOILER: | | | SHOW THE TYPE AND SIZE OF EXHAUST VENT, EXHAUST VENT | | | RUN AND TERMINATION LOCATION, AND SUBMIT MANUFACTURER'S | | | SPECIFICATIONS. | | | 3) REFER TO SECTION 1006.6- SAFETY AND RELIEF VALVE | | | DISCHARGE: "HIGH PRESSURE-STEAM SAFETY VALVES SHALL BE | | | VENTED TO THE OUTSIDE OF THE STRUCTURE" PLEASE PROVIDE | | | DETAILS. | | | 4) REFER TO SECTION 1008.1 AND INDICATE COMPLIANCE FOR | | | THE REQUIRED BLOWOFF VALVE AND BLOWOFF VALVE DISCHARGE | | | LOCATION. | | | 5) PROVIDE PIPING DIAGRAMS OR SCHEMATICS FOR THE BOILER | | | AND OTHER EQUIPMENT ASSOCIATED WITH THE SYSTEM. | | | INDICATE THE TYPES AND SIZES OF ALL PIPING, VALVE TYPES | | | AND LOCATIONS ETC. | | | 6) PROVIDE UL TESTED AND APPROVED FIRESTOPPING DETAILS | | | FOR ALL PIPES AND DUCTS PENETRATING THE FIRE-RATED | | | BOILER ENCLOSURE AND THE ROOF STRUCTURE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|