Plan Review Notes
Plan Review Notes For Permit 15090929
Permit Number 15090929
Review Stop G
Sequence Number 1
Notes
Date Text
2015-12-20 09:01:421) INDICATE ON THE PLAN THE VENTING CATEGORY OF THE
 BOILER IN ACCORDANCE WITH THE 2014 FBC-FUEL GAS SEC.
 202 (DEFINITIONS - VENTED APPLIANCE CATEGORIES).
 2) SHOW THE SIZE OF THE GAS VENT FOR THE BOILER. THE
 VENT SIZE SHALL COMPLY WITH SEC. 503.6.9 & TABLE
 504.2(2) IF THIS IS A CATEGORY I VENTED APPLIANCE. IF
 NOT A CATEGORY I APPLIANCE, SUBMIT MANUF. SPECS FOR THE
 REQUIRED VENT SIZING.
 3) SHT.P-200 - INDICATE THE TYPE OF MATERIAL, LOCATION
 AND DISTANCE ABOVE THE ROOF OF THE VENTS FOR THE
 BLOWDOWN TANKS FOR THE BOILER, FEEDWATER TANK AND THE
 AUTOCLAVE.SUBMIT MANUFACTURER'S SPECS FOR THE VENT
 INSTALLATION FOR THIS EQUIPMENT. WPB AMEND. TO FBC SEC.
 107.2.1.
 4) A TYPE B GAS VENT SHALL TERMINATE AT LEAST 5 FEET IN
 VERTICAL HEIGHT ABOVE THE APPLIANCE DRAFT HOOD OR FLUE
 COLLAR PER 2014 FGC SEC.503.6.5. SHOW ON THE THE PLANS.
 SHOW THE TOTAL HEIGHT OF THE GAS VENT.
 5) INDICATE ON THE PLAN IF THE BOILER IS A NATURAL
 DRAFT OR FAN ASSISTED VENT APPLIANCE. THIS WILL
 DETERMINE VENT SIZE IF A CATEGORY I VENTED APPLIANCE
 PER TABLE 504.2 (2).
 6) SUBMIT DETAILS FOR SUPPORT OF THE GAS VENT. 2014 FGC
 SEC.503.6.1.
 7) SHOW THE SIZE OF THE LP TANKS ON THE PLAN.WPB AMEND.
 TO FBC SEC. 107.2.1.
 8) SUBMIT ANCHORING DETAILS FOR THE LP TANKS.ANCHORING
 SHALL BE DDESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 BUILDING SEC.1609.
 9) SHT. P-100 - THE SIZE OF THE PIPING FROM THE LP
 TANKS IS SHOWN AS 3/4 INCH BUT THE BOILER SYSTEM DETAIL
 SHOWS 1 1/4 INCHES. CLARIFY.
 10) SUBMIT DETAILS FOR THE SEALING OF THE GAS PIPE
 PENETRATION THROUGH THE EXTERIOR WALL. WPB AMEND. TO
 FBC SEC. 107.2.1.
 11) SHOW THE LOCATION OF THE STEP DOWN GAS REGULATOR ON
 THE GAS DRAWING.WPB AMEND. TO FBC SEC. 107.2.1.
 12) SHOW THE DISTANCE FROM THE STEP DOWN REGULATOR TO
 THE MOST REMOTE OUTLET ON THE SYSTEM.WPB AMEND. TO FBC
 SEC. 107.2.1.
 13) SHOW THE PIPE SIZE FROM THE STEP DOWN REGULATOR TO
 THE EQUIPMENT.WPB AMEND. TO FBC SEC. 107.2.1.
 14) SHOW THE SIZE OF THE GAS PIPING FROM THE LP
 TANKS.WPB AMEND. TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  