2015-10-02 10:14:06PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE SECOND ELECTRICAL REVIEW OF
 THE ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
 1. YOU SHALL SUBMIT ELECTRICAL DRAWINGS INDICATING THE
 SCOPE OF WORK.
 2. THE SPECS ON THE BOILER DO NOT INDICATE WHICH OF THE
 CHOICES FOR THE PUMPS ETC.
 3. YOU SHALL PROVIDE THE REQUIRED LIGHTING AND SERVICE
 OUTLET FOR THE NEW BOILER ROOM.
 4. YOU WILL SUBMIT A SIMPLE FEEDER SCHEDULE (RISER
 DIAGRAM) INDICATING THE WIRE SIZE, INSULATION AND ALL
 APPLICABLE COMPONENTS OF THE INSTALLATION.
 5.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  