| 2015-10-05 06:33:41 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15090929 |
| | ADD: 1044 26TH ST. |
| | CONT: JOSEPH W. SCHUESSLER, INC. |
| | TEL: (561)635-6712 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. OCT. 5/2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 1SHOWS A BOILER WITHIN NEW 1 HOUR FIRE RATED |
| | WALLS. THE PLANS DO NOT PROVIDE AT WHAT PRESSURE AND |
| | THE HORSEPOWER OF THE MOTOR. IF THE BOILER IS OVER 15 |
| | PSI AND 10 HORSEPOWER THEN IT WOULD REQUIRE EITHER A 1 |
| | HOUR FIRE RATED ROOM OR AN AUTOMATIC FIRE SPRINKLER |
| | SYSTEM. 2014 FBC-B TABLE 509. THE PLANS DO INDICATE A 1 |
| | HOUR FIRE RATED ROOM, IF THE BOILERS OPERATING PRESSURE |
| | IS OVER 15 PSI AND MOTOR IS OVER 10 HORSEPOWER THEN THE |
| | DOOR WILL NEED TO BE 3/4 HR RATING IN COMPLIANCE WITH |
| | TABLE 716.5. |
| | |
| | 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |