2015-10-05 06:33:41BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090929
 ADD: 1044 26TH ST.
 CONT: JOSEPH W. SCHUESSLER, INC.
 TEL: (561)635-6712
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT. 5/2015
 ACTION: DENIED
  
 1) SHEET 1SHOWS A BOILER WITHIN NEW 1 HOUR FIRE RATED
 WALLS. THE PLANS DO NOT PROVIDE AT WHAT PRESSURE AND
 THE HORSEPOWER OF THE MOTOR. IF THE BOILER IS OVER 15
 PSI AND 10 HORSEPOWER THEN IT WOULD REQUIRE EITHER A 1
 HOUR FIRE RATED ROOM OR AN AUTOMATIC FIRE SPRINKLER
 SYSTEM. 2014 FBC-B TABLE 509. THE PLANS DO INDICATE A 1
 HOUR FIRE RATED ROOM, IF THE BOILERS OPERATING PRESSURE
 IS OVER 15 PSI AND MOTOR IS OVER 10 HORSEPOWER THEN THE
 DOOR WILL NEED TO BE 3/4 HR RATING IN COMPLIANCE WITH
 TABLE 716.5.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  