| Plan Review Notes For Permit 15090923 |
| Permit Number |
15090923 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-22 17:40:58 | ****CORRECTIONS**** | | | | | | ART LANGE - BUILDING INSPECTOR | | | 561-805-6667 [email protected] | | | FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA | | | RESIDENTIAL CODE 2015 5TH EDITION | | | | | | 1. ONE SET OF PLANS PROVIDED HAVE NOT BEEN SIGNED AND | | | SEALED. | | | THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A | | | REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY | | | CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA | | | ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES & | | | 61G1 FLORIDA ADMINISTRATIVE CODE. | | | | | | 2. PERMIT DESCRIPTION OF WORK DOES NOT REFLECT WHAT HAS | | | BEEN SUBMITTED. | | | | | | 3. PLEASE PROVIDE THE DESIGN CRITERIA FOR THE 2 HOUR | | | RATING ON WALL NUMBER 9. | | | | | | 4. WILL DOOR NUMBER 3 HAVE A LINTEL OR BEAM ABOVE IT. | | | PLEASE PROVIDE A DETAILS ON PLANS. | | | | | | 5. WILL ANY NEW ELECTRICAL BE REQUIRED FOR OHD OPENER | | | OR RELOCATED WITH THE NEW WALLS. | | | |
|