| Plan Review Notes For Permit 15090913 |
| Permit Number |
15090913 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-22 19:10:33 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY THE SLOPE OF THE PITCHED ROOF AND THE MEAN | | | ROOF HEIGHT. FBC 107.2.1 & FBC-R905.3.2 | | | | | | 2) SPECIFY THE TILE PROFILE. FBC 107.2.1 & FBC-R905.3 | | | | | | 3) SPECIFY THE PATTY SIZE AND WHETHER THE APPLICATION | | | IS INTER-DEPENDENT OR INDEPENDENT AS SPECIFIED IN THE | | | PRODUCT APPROVALS. FBC 107.2.1 & FBC-R905.3 |
|