| Date |
Text |
| 2015-09-23 08:36:57 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | 1) THE REMOVAL AND CAPPING OF THE FIRE HOSE CABINET IS |
| | NOT APPROVED UNDER THIS PERMIT. |
| | |
| | |
| | 2) THE REQUEST FOR REMOVAL OF THE FIRE HOSE MAY BE |
| | SUBMITTED SEPARATELY TO THE FIRE MARSHALS OFFICE AND IN |
| | COMPLIANCE WITH THE REQUIREMENTS OF NFPA. |
| | |
| | NFPA 14--, STANDARD FOR THE INSTALLATION OF STANDPIPE |
| | AND HOSE SYSTEMS DETAILS THE DESIGN AND INSTALLATION OF |
| | STANDPIPE SYSTEMS. |
| | 7.3.4 CLASS III SYSTEMS. CLASS III SYSTEMS SHALL BE |
| | PROVIDED WITH HOSE CONNECTIONS AS REQUIRED FOR BOTH |
| | CLASS I AND CLASS II SYSTEMS. |
| | 7.3.4.1 WHERE THE BUILDING IS PROTECTED THROUGHOUT BY |
| | AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH NFPA 13, STANDARD FOR THE INSTALLATION OF |
| | SPRINKLER SYSTEMS, AND NFPA 13R, STANDARD FOR THE |
| | INSTALLATION OF SPRINKLER SYSTEMS IN RESIDENTIAL |
| | OCCUPANCIES UP TO FOUR STORIES IN HEIGHT, CLASS II HOSE |
| | STATIONS FOR USE BY TRAINED PERSONNEL SHALL NOT BE |
| | REQUIRED, SUBJECT TO THE APPROVAL OF THE LOCAL FIRE |
| | DEPARTMENT, PROVIDED THAT EACH CLASS I HOSE CONNECTION |
| | IS 2 1/2 IN. AND IS EQUIPPED WITH A 2 1/2 IN. ? 1 1/2 |
| | IN. REDUCER AND A CAP ATTACHED WITH A CHAIN. |
| | |