| Plan Review Notes For Permit 15090855 |
| Permit Number |
15090855 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-11-29 07:21:21 | 1) THE ISLAND SINK DETAIL SHOWS A FLAT DRY VENT | | | CONNECTED TO A SANITARY TEE ( SEE KEYED NOTE #3). DRY | | | VENT CONNECTIONS TO A HORIZONTAL DRAIN SHALL CONNECT | | | ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE PER | | | FBC-PLUMBING SEC.905.3. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|