| Plan Review Notes For Permit 15090855 |
| Permit Number |
15090855 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-11-24 07:48:32 | 2ND REVIEW 2014 MECHANICAL | | | PERMIT #15090855 | | | 11/24/15 | | | | | | 1) TWO SEPARATE ENERGY GAUGE PERFORMANCE CALCULATIONS | | | HAVE BEEN SUBMITTED: PLEASE REMOVE THE OUTDATED FORM | | | 506-2010, AND RE-SUBMIT FORM 506-2014 WITH THE COVER | | | SHEET ATTACHED AT THE FRONT OF THE DOCUMENT AND THE | | | MANDATORY REQUIREMENTS CHECKLIST FILLED OUT. | | | 2) AS PREVIOUSLY REQUESTED SHOW A MEANS OF SERVICE | | | ACCESS FOR THE ROOFTOP MECHANICAL EQUIPMENT- SEE | | | SECTION 306.5 FBC-14 MECHANICAL. | | | 3) THE WIND LOAD SUBMITTAL FROM THE ENGINEER OF RECORD | | | DOES NOT SPECIFY THE SIZE DIMENSIONS OR GAUGE FOR THE | | | STEEL CLIPS USED TO TIE THE RTU'S TO THE CURB- PLEASE | | | PROVIDE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|