Plan Review Notes
Plan Review Notes For Permit 15090855
Permit Number 15090855
Review Stop M
Sequence Number 2
Notes
Date Text
2015-11-24 07:48:322ND REVIEW 2014 MECHANICAL
 PERMIT #15090855
 11/24/15
  
 1) TWO SEPARATE ENERGY GAUGE PERFORMANCE CALCULATIONS
 HAVE BEEN SUBMITTED: PLEASE REMOVE THE OUTDATED FORM
 506-2010, AND RE-SUBMIT FORM 506-2014 WITH THE COVER
 SHEET ATTACHED AT THE FRONT OF THE DOCUMENT AND THE
 MANDATORY REQUIREMENTS CHECKLIST FILLED OUT.
 2) AS PREVIOUSLY REQUESTED SHOW A MEANS OF SERVICE
 ACCESS FOR THE ROOFTOP MECHANICAL EQUIPMENT- SEE
 SECTION 306.5 FBC-14 MECHANICAL.
 3) THE WIND LOAD SUBMITTAL FROM THE ENGINEER OF RECORD
 DOES NOT SPECIFY THE SIZE DIMENSIONS OR GAUGE FOR THE
 STEEL CLIPS USED TO TIE THE RTU'S TO THE CURB- PLEASE
 PROVIDE.
  