Plan Review Notes For Permit 15090855 |
Permit Number |
15090855 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-11-29 07:14:23 | 1) SUBMIT DETAILS ON THE PLAN AS TO HOW THE GAS STANDS | | ARE TO BE ATTACHED TO THE ROOF ( TYPE, DIAMETER & | | LENGTH OF FASTENERS, SPACING, ETC.).WPB AMEND. TO FBC | | SEC. 107.2.1. | | 2) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS | | APPLIANCES IN ACCORDANCE WITH THE 2014 FBC-FUEL GAS | | SEC.304. WHERE COMBUSTION AIR IS PROVIDED BY THE | | BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM | | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN | | ADDITION TO THE REQUIRED VENTILATION AIR.2014 FBC | | SEC.304.9.3. THIS WAS OVERLOOKED IN MY FIRST REVIEW. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|