Plan Review Notes
Plan Review Notes For Permit 15090855
Permit Number 15090855
Review Stop G
Sequence Number 2
Notes
Date Text
2015-11-29 07:14:231) SUBMIT DETAILS ON THE PLAN AS TO HOW THE GAS STANDS
 ARE TO BE ATTACHED TO THE ROOF ( TYPE, DIAMETER &
 LENGTH OF FASTENERS, SPACING, ETC.).WPB AMEND. TO FBC
 SEC. 107.2.1.
 2) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES IN ACCORDANCE WITH THE 2014 FBC-FUEL GAS
 SEC.304. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR.2014 FBC
 SEC.304.9.3. THIS WAS OVERLOOKED IN MY FIRST REVIEW.
  