2015-11-25 11:36:32 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15090855 |
| ADD: 1703 PALM BEACH LAKES SUITE # H03 |
| CONT: TBD |
| TEL: (561)348-4805 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2ND REVIEW |
| DATE: WED. NOV. 25/2015 |
| ACTION: DENIED |
| |
| 1)2ND REQUEST. |
| 1A) SHEET A101 NOTES 13 & 15 SHOW A NEW EXTERIOR DOOR, |
| TRANSOM & SIDELIGHT WINDOW. SHEET A401 SHOW THE |
| ELEVATION AND DIMENSIONS FOR THE NEW OPENING. THIS |
| REVIEW NO PRODUCT APPROVALS WERE SUBMITTED. PLEASE SHOW |
| COMPLIANCE WITH : |
| 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. SUBMIT (2) APPROVALS, ONLY 1 |
| SUBMITTED, NOT REVIEWED BY THE DESIGNER OF |
| RECORD. |
| (B) WINDOWS. . SUBMIT (2) APPROVALS, ONLY 1 SUBMITTED, |
| NOT REVIEWED BY THE DESIGNER OF RECORD. |
| (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES ( CURBS FOR INTAKE |
| AND EXHAUST FANS). NO PRODUCT APPROVALS |
| WERE SUBMITTED FOR THE ROOFING REPAIRS, CURBS NOR ROOF |
| TOP FAN OR OTHER EQUIPMENT. |
| |
| 1B) SUBMIT (2) OF ALL PRODUCT APPROVALS. 107.1 GENERAL. |
| SUBMITTAL DOCUMENTS CONSISTING OF CONSTRUCTION |
| DOCUMENTS, STATEMENT OF SPECIAL INSPECTIONS, |
| GEOTECHNICAL REPORT AND OTHER DATA SHALL BE SUBMITTED |
| IN TWO OR MORE SETS WITH EACH PERMIT APPLICATION. |
| |
| 1C) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| 2) 2ND REQUEST. SEMI ?COMPLIED. WITH THE MENTION ABOVE |
| OF THE NEW CURBS, ROOF TOP UNITS AND EXHAUST FANS IT |
| WAS ASSUMED THAT ROOF TOP PRESSURES FOR ZONES 1, 2 & 3 |
| WOULD BE SUBMITTED IN VULT AND VASD. |
| |
| 1ST ROUND OF COMMENTS. WITH THE NEW DOOR AND WINDOW |
| OPENINGS PLEASE PROVIDE THE WIND DESIGN CRITERIA . |
| 2014 FBC-B 1603.1.4 WIND DESIGN DATA. NOTE SHEET A101 |
| REFERENCE?S THE WIND DESIGN OF 140, VASD, THIS WAS |
| UNDER THE 2010 FBC. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| |
| 2.2. RISK CATEGORY. |
| |
| 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. |
| |
| 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| M2). |
| |
| 2.6TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. |
| |
| 2.7 PLEASE CONVERT PRESSURES FROM VULT TO VASD SINCE |
| ALL OF THE TESTING FOR THE PRODUCT APPROVALS ARE IN |
| VASD. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| |
| 3) 2ND REQUEST. SHEET S1.0 TYPICAL ROOF TOP MECHANICAL |
| UNIT SUPPORT. THIS DETAIL DOESN?T FIT THIS APPLICATION. |
| THE ROOF TOP UNITS SIT ON A PRE-MANUFACTURED CURB. THIS |
| DETAIL IS SIMILAR TO BACK WHEN 4X4 SLEEPERS WERE |
| ATTACHED TO THE ROOF DECK WITH PITCH PANS. THE CODE |
| REQUIRES EITHER CURBS FOR DOWN UNITS OR FOR REMOTE |
| CONDENSING UNITS COMPLIANCE WITH 2014 FBC-B TABLE |
| 1509.6.5 CLEARANCE BELOW RAISED ROOF MOUNTED MECHANICAL |
| UNITS. |
| 1ST REVIEW COMMENT. SHEET A301 & M103 BOTH SHOW GENERIC |
| HOOD, INTAKE AND EXHAUST FANS AND CURBS. PLEASE PROVIDE |
| THE STRUCTURAL DETAILS FOR THE RE-ENFORCEMENT OF THE |
| BAR JOIST AND THE STEEL ANGLE IRON RE-ENFORCEMENT THAT |
| WILL BE USED TO ANCHOR THE ROOF TOP CURB FOR BOTH THE |
| INTAKE AND EXHAUST FANS. THIS WILL BE PART OF THE MWFRS |
| MAIN WIND FORCE RESISTING SYSTEM. |
| |
| 4) 2ND REQUEST. PLEASE SHOW COMPLIANCE WITH ROOF TOP |
| ACCESS TO THE MECHANICAL EQUIPMENT ON THE ROOF. |
| A 11X17 SHEET WITH CUHACI & PETERSON ARCHITECTS ROOF |
| PLAN WAS SUBMITTED. NOTE THIS SHEET WAS NOT SIGNED NOR |
| SEALED. |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| FL ADMIN CODE 61G16.003 ARCHITECTS. |
| THIS ROOFTOP PLAN DOES SHOW COMPLIANCE FOR ROOF TOP |
| ACCESS. IF SIGNED AND SEALED IT WOULD MEET CODE |
| COMPLIANCE. |
| |
| 1ST ROUND COMMENT. PLEASE SHOW COMPLIANCE WITH ROOF TOP |
| ACCESS TO THE MECHANICAL EQUIPMENT ON THE ROOF. THE |
| PLANS DO NOT INDICATE COMPLIANCE WITH: |
| 2014 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS |
| OR ELEVATED STRUCTURES. |
| WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE |
| INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT |
| EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE |
| PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE |
| EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO |
| THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH |
| ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS |
| GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON |
| ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN |
| 12 UNITS HORIZONTAL (33-PERCENT SLOPE). |
| PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED |
| ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN |
| CRITERIA: |
| 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR |
| ROOF EDGE NOT LESS THAN 30 INCHES (762 MM). |
| 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14 |
| INCHES (356 MM) ON CENTER. |
| 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN |
| 6-INCHES (152 MM) DEEP. |
| 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM) |
| BETWEEN RAILS. |
| 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM) |
| DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND |
| (136.1 KG) LOAD. |
| 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE |
| PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF |
| WITHSTANDING 100 POUNDS PER SQUARE FOOT (488.2 KG/M2). |
| 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY |
| APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE |
| REQUIRED ACCESS SHALL BE NOT LESS THAN 24-INCHES (610 |
| MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR |
| SERVICE PLATFORMS |
| |
| 5) SEMI-COMPLIED. THE NEW S1.0 DOES PROVIDE DETAILS OF |
| A ROOF TOP CONDENSING UNIT BEING TIED DOWN WITH CLIPS |
| L2X2X16 GAX0?-4? LG. |
| (2)@ EA. CORNER (8) TOTAL |
| W/(2) # 10-16 TEK EACH LEG. |
| THERE ARE 2 QUESTIONS, (1) TYPE OF MATERIAL ARE THE |
| CLIPS? |
| 2ND 8 ? X 11 SHEETS SIGNED AND SEALED BY NICHOLAS |
| STEINERT DOES NOT REFERENCE HOW MANY SHEETS ARE COVERED |
| UNDER THIS SEAL, NO INDEX ON THE SEALED SHEET |
| (61G15-23.002(2) FL. ADMIN. CODE). THE LAST SHEET OF |
| ENGINEERING REFERENCES CLIPS BUT THE SIZE AND MATERIAL |
| OF THE CLIPS IS NOT PROVIDED. |
| |
| 1ST REVIEW COMMENT. NEITHER THE ARCHITECTURAL NOR |
| MECHANICAL PLANS PROVIDE HOW THE ROOF TOP FANS ARE |
| GOING TO BE ANCHORED TO THE CURB TO RESIST THE MOMENT |
| OF OVERTURNING. COMPONENTS AND CLADDING. 1609.6.4.4.1. |
| |
| 6) COMPLIED. |
| |
| 7) NOTE ALL WIELDING ON THE ROOF FRAMING MEMBERS, BAR |
| JOIST AND ROOF DECK WILL NEED 3RD PARTY CERTIFICATION |
| FOR WELDS. 110.3.9.1 AFFIDAVIT FOR INSPECTION. WITH |
| SPECIFIC PRIOR APPROVAL OF, AND IN A FORMAT ACCEPTABLE |
| TO THE BUILDING OFFICIAL, AN AFFIDAVIT FOR |
| CERTIFICATION OF INSPECTION MAY BE ACCEPTED FROM THE |
| 3RD PARTY INSPECTOR. CONTACT KEN CONRAD MANAGER OF THE |
| THRESHOLD & SPECIAL INSPECTOR PROGRAM. |
| KEN CONRAD |
| TEL: (561)805-6666 |
| E-MAIL: [email protected] |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |