2015-11-25 11:36:32BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090855
 ADD: 1703 PALM BEACH LAKES SUITE # H03
 CONT: TBD
 TEL: (561)348-4805
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: WED. NOV. 25/2015
 ACTION: DENIED
  
 1)2ND REQUEST.
 1A) SHEET A101 NOTES 13 & 15 SHOW A NEW EXTERIOR DOOR,
 TRANSOM & SIDELIGHT WINDOW. SHEET A401 SHOW THE
 ELEVATION AND DIMENSIONS FOR THE NEW OPENING. THIS
 REVIEW NO PRODUCT APPROVALS WERE SUBMITTED. PLEASE SHOW
 COMPLIANCE WITH :
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. SUBMIT (2) APPROVALS, ONLY 1
 SUBMITTED, NOT REVIEWED BY THE DESIGNER OF
 RECORD.
 (B) WINDOWS. . SUBMIT (2) APPROVALS, ONLY 1 SUBMITTED,
 NOT REVIEWED BY THE DESIGNER OF RECORD.
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES ( CURBS FOR INTAKE
 AND EXHAUST FANS). NO PRODUCT APPROVALS
 WERE SUBMITTED FOR THE ROOFING REPAIRS, CURBS NOR ROOF
 TOP FAN OR OTHER EQUIPMENT.
  
 1B) SUBMIT (2) OF ALL PRODUCT APPROVALS. 107.1 GENERAL.
 SUBMITTAL DOCUMENTS CONSISTING OF CONSTRUCTION
 DOCUMENTS, STATEMENT OF SPECIAL INSPECTIONS,
 GEOTECHNICAL REPORT AND OTHER DATA SHALL BE SUBMITTED
 IN TWO OR MORE SETS WITH EACH PERMIT APPLICATION.
  
 1C) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 2) 2ND REQUEST. SEMI ?COMPLIED. WITH THE MENTION ABOVE
 OF THE NEW CURBS, ROOF TOP UNITS AND EXHAUST FANS IT
 WAS ASSUMED THAT ROOF TOP PRESSURES FOR ZONES 1, 2 & 3
 WOULD BE SUBMITTED IN VULT AND VASD.
  
 1ST ROUND OF COMMENTS. WITH THE NEW DOOR AND WINDOW
 OPENINGS PLEASE PROVIDE THE WIND DESIGN CRITERIA .
 2014 FBC-B 1603.1.4 WIND DESIGN DATA. NOTE SHEET A101
 REFERENCE?S THE WIND DESIGN OF 140, VASD, THIS WAS
 UNDER THE 2010 FBC.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2.2. RISK CATEGORY.
  
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 2.6TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 2.7 PLEASE CONVERT PRESSURES FROM VULT TO VASD SINCE
 ALL OF THE TESTING FOR THE PRODUCT APPROVALS ARE IN
 VASD. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 3) 2ND REQUEST. SHEET S1.0 TYPICAL ROOF TOP MECHANICAL
 UNIT SUPPORT. THIS DETAIL DOESN?T FIT THIS APPLICATION.
 THE ROOF TOP UNITS SIT ON A PRE-MANUFACTURED CURB. THIS
 DETAIL IS SIMILAR TO BACK WHEN 4X4 SLEEPERS WERE
 ATTACHED TO THE ROOF DECK WITH PITCH PANS. THE CODE
 REQUIRES EITHER CURBS FOR DOWN UNITS OR FOR REMOTE
 CONDENSING UNITS COMPLIANCE WITH 2014 FBC-B TABLE
 1509.6.5 CLEARANCE BELOW RAISED ROOF MOUNTED MECHANICAL
 UNITS.
 1ST REVIEW COMMENT. SHEET A301 & M103 BOTH SHOW GENERIC
 HOOD, INTAKE AND EXHAUST FANS AND CURBS. PLEASE PROVIDE
 THE STRUCTURAL DETAILS FOR THE RE-ENFORCEMENT OF THE
 BAR JOIST AND THE STEEL ANGLE IRON RE-ENFORCEMENT THAT
 WILL BE USED TO ANCHOR THE ROOF TOP CURB FOR BOTH THE
 INTAKE AND EXHAUST FANS. THIS WILL BE PART OF THE MWFRS
 MAIN WIND FORCE RESISTING SYSTEM.
  
 4) 2ND REQUEST. PLEASE SHOW COMPLIANCE WITH ROOF TOP
 ACCESS TO THE MECHANICAL EQUIPMENT ON THE ROOF.
 A 11X17 SHEET WITH CUHACI & PETERSON ARCHITECTS ROOF
 PLAN WAS SUBMITTED. NOTE THIS SHEET WAS NOT SIGNED NOR
 SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G16.003 ARCHITECTS.
 THIS ROOFTOP PLAN DOES SHOW COMPLIANCE FOR ROOF TOP
 ACCESS. IF SIGNED AND SEALED IT WOULD MEET CODE
 COMPLIANCE.
  
 1ST ROUND COMMENT. PLEASE SHOW COMPLIANCE WITH ROOF TOP
 ACCESS TO THE MECHANICAL EQUIPMENT ON THE ROOF. THE
 PLANS DO NOT INDICATE COMPLIANCE WITH:
 2014 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS
 OR ELEVATED STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON
 ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN
 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES (762 MM).
 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES (356 MM) ON CENTER.
 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN
 6-INCHES (152 MM) DEEP.
 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM)
 BETWEEN RAILS.
 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM)
 DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND
 (136.1 KG) LOAD.
 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE
 PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF
 WITHSTANDING 100 POUNDS PER SQUARE FOOT (488.2 KG/M2).
 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE
 REQUIRED ACCESS SHALL BE NOT LESS THAN 24-INCHES (610
 MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR
 SERVICE PLATFORMS
  
 5) SEMI-COMPLIED. THE NEW S1.0 DOES PROVIDE DETAILS OF
 A ROOF TOP CONDENSING UNIT BEING TIED DOWN WITH CLIPS
 L2X2X16 GAX0?-4? LG.
 (2)@ EA. CORNER (8) TOTAL
 W/(2) # 10-16 TEK EACH LEG.
 THERE ARE 2 QUESTIONS, (1) TYPE OF MATERIAL ARE THE
 CLIPS?
 2ND 8 ? X 11 SHEETS SIGNED AND SEALED BY NICHOLAS
 STEINERT DOES NOT REFERENCE HOW MANY SHEETS ARE COVERED
 UNDER THIS SEAL, NO INDEX ON THE SEALED SHEET
 (61G15-23.002(2) FL. ADMIN. CODE). THE LAST SHEET OF
 ENGINEERING REFERENCES CLIPS BUT THE SIZE AND MATERIAL
 OF THE CLIPS IS NOT PROVIDED.
  
 1ST REVIEW COMMENT. NEITHER THE ARCHITECTURAL NOR
 MECHANICAL PLANS PROVIDE HOW THE ROOF TOP FANS ARE
 GOING TO BE ANCHORED TO THE CURB TO RESIST THE MOMENT
 OF OVERTURNING. COMPONENTS AND CLADDING. 1609.6.4.4.1.
  
 6) COMPLIED.
  
 7) NOTE ALL WIELDING ON THE ROOF FRAMING MEMBERS, BAR
 JOIST AND ROOF DECK WILL NEED 3RD PARTY CERTIFICATION
 FOR WELDS. 110.3.9.1 AFFIDAVIT FOR INSPECTION. WITH
 SPECIFIC PRIOR APPROVAL OF, AND IN A FORMAT ACCEPTABLE
 TO THE BUILDING OFFICIAL, AN AFFIDAVIT FOR
 CERTIFICATION OF INSPECTION MAY BE ACCEPTED FROM THE
 3RD PARTY INSPECTOR. CONTACT KEN CONRAD MANAGER OF THE
 THRESHOLD & SPECIAL INSPECTOR PROGRAM.
 KEN CONRAD
 TEL: (561)805-6666
 E-MAIL: [email protected]
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER