| Plan Review Notes For Permit 15090855 |
| Permit Number |
15090855 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-03 05:49:52 | 1) SHT. P101- THE GREASE TRAP SIZING CALCULATIONS REFER | | | TO THE 2010 FLORIDA PLUMBING CODE. REVISE THE NOTE TO | | | READ THE 2014 FLORIDA PLUMBING CODE. | | | 2) ANY FLOOR DRAIN NOT RECEIVING THE DISCHARGE OF AN | | | INDIRECT WASTE SHALL BE EQUIPPED WITH A TRAP PRIMER PER | | | FBC-PLUMBING SEC.1002.4. | | | 3) CLEANOUTS ARE REQUIRED ON THE RISERS FOR THE ISLAND | | | VENT PER 2014 FBC- PLUMBING SEC.916.3. | | | 4) SHOW FIXTURES # K28, K32 & K73 ON THE SANITARY | | | DRAINAGE PLAN. | | | 5) SHOW THE LOCATION OF THE GREASE TRAPS ON THE PLAN. | | | WPB AMEND. TO FBC SEC. 107.2.1. | | | 6) ARE THE GREASE TRAPS SERVING ANY OTHER RESTAURANT | | | BESIDES THIS ONE?. INDICATE ON THE PLANS. IF SO, SUBMIT | | | REVISED SIZING CALCS. | | | 7) SHT. P103-DETAIL #5 - INDICATE ON THE PLAN HOW THE | | | GAS PIPE SUPPORTS WILL BE ATTACHED TO THE ROOF. | | | 8) INDICATE THE TYPE OF GAS PIPE TO BE INSTALLED. | | | 9) SUBMIT MANUF. SPECS FOR THE GAS REGULATORS. | | | 10) SUBMIT MANUF. SPECS ON ALL GAS EQUIPMENT. EQUIPMENT | | | SHALL BE LISTED AND LABELED PER FBC-GAS SEC. 301.3. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|