Plan Review Notes
Plan Review Notes For Permit 15090855
Permit Number 15090855
Review Stop M
Sequence Number 1
Notes
Date Text
2015-09-30 16:41:071ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090855
 9/30/15
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW RTU'S IN COMPLIANCE WITH SECTION C403.2.1 FBC-14
 ENERGY CONSERVATION.
 2) PROVIDE ENERGY CALCULATIONS FOR THE PROPOSED NEW
 RESTAURANT IN ACCORDANCE WITH C101.4.3 FBC-14 ENERGY
 CONSERVATION.
 3) SHEET M101: THE PLAN SHOWS DUCT SMOKE DETECTORS IN
 THE SUPPLY DUCTS OF THE RTU'S, HOWEVER THE DEVICES ARE
 REQUIRED TO BE INSTALLED IN THE RETURN AIR SYSTEMS- SEE
 SECTION 606.2.1 FBC-14 MECHANICAL.
 4) M103: SITE SPECIFIC WIND LOAD TIE DOWN ENGINEERING
 IS REQUIRED FOR INSTALLATION OF THE RTU'S, CONDENSERS,
 AND ROOF FANS- SEE SECTION 301.15 FBC-14 MECHANICAL.
 THE ENGINEER OF RECORD MUST PROVIDE WIND LOAD DESIGN
 CRITERA, DESIGN PRESSURES, AND COMPLETE DETAILS FOR TIE
 DOWN OF THE APPLIANCES. PLEASE NOTE THAT STRUTURAL
 DETAILS FOR THE ROOF OPENINGS SHALL ALSO BE PROVIDED.
 5) PLACE A NOTE ON THE PLANS INDICATING SEPARATE
 PERMITS ARE REQUIRED FOR THE KITCHEN HOOD & EXHAUST
 SYSTEM, DISHWASHER HOOD AND EXHAUST SYSTEM, AND THE
 WALK-IN COOLERS AND FREEZERS.
 6) THE PLANS DON'T INDICATE HOW SERVICE ACCESS IS BEING
 PROVIDED FOR THE ROOFTOP MECHANICAL EQUIPMENT: REFER TO
 SECTION 306.5 FBC-14 MECHANICAL AND SHOW COMPLIANCE.
 7) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AC
 EQUIPMENT INCLUDING THE THE TYPE AND SIZE OF PIPING,
 PIPING RUNS, PIPING DISCHARGE LOCATIONS, AND PIPI NG
 SUPPORT AND PROTECTION- SEESECTION 307 FBC-14
 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  