| Plan Review Notes For Permit 15090835 |
| Permit Number |
15090835 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-09-24 12:09:21 | 9/24/15 - PROVISO | | | 1. ALARM SYSTEM SHALL BE 3RD PARTY CERTIFICATED | | | 2. ENSURE THAT AUDIBLE AND VISIBLE SPECS ARE MET AND | | | COMPLIANT WITH NFPA 72. CURRENT PLAN APPEARS TO HAVE | | | SOME ROOMS THAT WILL NOT MEET AUDIBLE REQUIREMENTS. | | | 3. THIS LOCATION HAS EXPERIENCED A SUBSTANTIAL NUMBER | | | OF FALSE ALARMS IN THE PAST, WHICH MAY IN PART BE DUE | | | TO THE DENSE SMOKE DETECTOR COVERAGE. EVALUATE WHETHER | | | THE PROPOSED DETECTION DEVICES AND | | | METHOD OF INITIATION WILL ALLEVIATE FALSE DETECTION | | | CREATED BY PARTICULATES SUCH AS DUST. | | | 4. CLASS "A" WIRING REQUIRED. | | | 5. INSTALL A WEATHER PROOF STROBE ON EXTERIOR OF BLDG | | | FACING ROADSIDE. |
|