| Plan Review Notes For Permit 15090823 |
| Permit Number |
15090823 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-03 07:04:49 | 1) ALL GAS APPLIANCES SHALL BE LISTED & LABELED PER THE | | | 2014 FBC-FUEL GAS SEC. 301.3. SUBMIT VERIFICATION OF | | | LISTING/LABELING. | | | 2) NOTE #3 ON PLAN REFERS TO SHT. LS 101H. THERE IS NO | | | SUCH SHEET IN THIS SUBMITTAL. SUBMIT THE SHEET FOR | | | REVIEW. WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) SUBMIT COMPLETE MANUF. SPECIFICATION SHEETS FOR THE | | | FIRE PIT. WPB AMEND. TO FBC SEC. 107.2.1. | | | 4) SUBMIT A SITE PLAN SHOWING THE LOCATION OF THE FIRE | | | PIT.WPB AMEND. TO FBC SEC. 107.2.1. | | | 5) INDICATE ON THE PLAN IF THE GAS IS LP OR NATURAL.WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 6) SUBMIT A GAS PIPING DIAGRAM SHOWING THE LOCATION OF | | | THE GAS METER/LP TANK, THE DISTANCE FROM THE THE | | | METER/TANK TO THE FIRE PIT, THE DISTANCE FROM THE METER | | | / TANK TO THE MOST REMOTE OUTLET ON THE SYSTEM, TYPE OF | | | PIPE, BTU LOAD OF APPLIANCE, ETC. SEE GAS PERMITTING | | | CHECKLIST IN PERMIT FOLDER. | | | 7) EXPLAIN THE REASON FOR THE VENTS LOCATED ON THE WALL | | | OF THE FIREPIT.WPB AMEND. TO FBC SEC. 107.2.1. | | | 8) EXPLAIN THE INSTALLATION OF THE TWO 9" CATCH BASINS | | | THAT APPEAR TO BE LOCATED IN THE PIT AND WHAT | | | DISCHARGES TO THESE DRAINS AND WWHERE DOES THE EFFLUENT | | | GO? | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|