| 2016-02-18 14:33:21 | 2ND ELECTRICAL REVIEW NOTES: |
| | REVIEWED FOR COMPLIANCE WITH: |
| | FBC 5TH EDITION 2014 |
| | NFPA 70 2011 (NEC) |
| | |
| | CORRECTIONS REQUIRED: |
| | 1. ACCEPTED RESPONSE WITH NOTE. |
| | 2. ACCEPTED RESPONSE. OUTLETS ARE INDICATED AND NOTE |
| | ALLOWING ADJUSTMENT DUE TO CONDITIONS. |
| | 3. THE RISER DIAGRAM REFLECTS A PANEL ?C? AS EXISTING, |
| | AND THE MDP CIRCUIT DIRECTORY REFERS TO FOOD PREP LINE, |
| | IS THAT THE SAME AS PANEL ?C?? IF SO, CORRECT THE |
| | LABELS TO MATCH. |
| | 4. PANEL ?C? SHOWN ON THE RISER DIAGRAM OR FOOD PREP |
| | LINE SHOWN ON THE MDP SCHEDULE DO NOT HAVE LOAD CALCS |
| | SHOWN ON PLAN. |
| | 5. THERE IS A CIRCUIT DIRECTORY FOR PANELS A & B, BUT |
| | NOT FOR C OR THE FOOD PREP LINE. |
| | 6. THERE IS NO INDICATION ON THE NOTES AREA NOR |
| | MARKINGS ON THE PANELS TO SHOW COMPLIANCE WITH THIS |
| | REQUIREMENT. PANELS SHALL BE MARKED TO INDICATE THE |
| | LOCATION OF THEIR SOURCE OF POWER. |
| | 7. ACCEPTED THAT THE RECESSED LIGHTS ARE NOT WITHIN THE |
| | THERMAL ENVELOPE. |
| | 8. THE EXISTING LIGHTING DESIGN MAY HAVE BEEN MADE TO |
| | AN EARLIER CODE WHICH HAD LESSER REQUIREMENTS. CURRENT |
| | CODES TAKE INTO ACCOUNT DAYLIGHT ENTERING THE PREMISES |
| | ALONG WITH DIMMING REQUIREMENTS. |
| | 9. THE FLACOM REPORT SUBMITTED IS OUTDATED. IT SHALL BE |
| | TO THE STANDARDS OF THE 2014 FBC. |
| | 10. ACCEPTED NEW SEPARATED SHEETS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |