2015-10-05 08:46:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090810
 ADD: 4385 45TH ST
 CONT: C. W. HAYES CONSTRUCTION CO.
 TEL: (407)366-1564
 E-MAIL: CWHAYESCONSTRUCTION.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT. 06/2015
 ACTION: DENIED
  
 1) SHEET S0-1 INDICATES THE CORRECT WIND DESIGN
 CRITERIA 170 MPH, EXPOSURE C BUT THE OPENING SIZE THE
 PRESSUES IS NOT GIVEN. ROOF PRESSURES ARE REVIEWED FOR
 10 SQ. FT. PRESSURES IN ROOF ZONES 1 & 2 ARE CORRECT
 PRESSURES IN ROOF ZONE 3 ARE PROVIDED AS ZONE # 2
 ASSUMED 3'-0" PARAPET. SHEET A4-0 SHOWS A DASH LINE
 ASSUMED TO BE THE ROOF WITH PARAPET AT 30 INCHES, NOT 3
 FEET. ASCE 7-10 REQUIRES A 3'-0" PARAPET NOT TO HAVE A
 ROOF ZONE 3.
  
 2) SHEET S0-1 INDICATES THE CORRECT WIND DESIGN
 CRITERIA 170 MPH, EXPOSURE C BUT THE OPENING SIZE THE
 PRESSUES IS NOT GIVEN. THE WINDOWS BEING REPLACED ARE
 IN A WALL ZONE 4, THE SIZE OF THE OPENING IN THE CHART
 IS NOT GIVEN. THEY ARE CLOSE TO 50 SQ. FT. PRESSURES IN
 WALL ZONE 4, EXPOSURE C @ 15 FEET MEAN ROOF HEIGHT ARE
 +33.9/ -37.1. PLEASE CORRECT. 2014 FBC-B 1603.1.4 WIND
 DESIGN DATA.
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31) (B) WINDOWS
 (C) WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) SHEET S4.1 AND DETAIL # 4 INDICATES THE SLAT WALL
 SYSTEM BY SPECIALTY ENGINEER. SHEET A4.0 NOTE # 12
 INDICATES THE SLAT WALL SYSTEM IS TO BE A ALUMINUM
 PRODUCT. BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT
 PLEASE HAVE ENGINEER OF RECORD REVIEW AND APPROVE
 BEFORE BEING FORWARDED TO THE BUILDING DEPARTMENT.
  
 SHEET A5.1 NOTE ON SHEET: DESIGN INTENT IS TO SPAN SLAT
 WALL BETWEEN TOWERS. SLAT WALL VENDOR TO DESIGN
 STRUCTURE REQUIRED FOR SPAN.
  
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 6) SHEET S4.2 DETAILS 1 & 3. THE PLANS ARE NOT CLEAR
 THE HOLES TO BE DRILLED INTO THE EXISTING FOUNDATION,
 HOW DEEP ARE THE HOLES TO BE DRILLED INTO THE
 FOUNDATION AND AT WHAT CENTERS? THE OTHER ISSUE, THERE
 THE REBAR PINS TO BE EPOXIED INTO PLACE? 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED. NOTE THE FOUNDATION
 EXTENSION IS PART OF THE MWFRS MAIN WIND FORCE
 RESISTING SYSTEM.
  
 7) SHEET A3.0 NOTE # 11 WHICH DEALS WITH ROOF TOP RTU'S
 OR ROOF TOP A/C STANDS. REPLACE OR RE-COMMISION TO
 CURRENT DESIGN LOADS. PLEASE PROVIDE WHAT THE INTENT OF
 THIS STATEMENT IS? THERE IS NO INFORMATION ON THE
 MECHANICAL SHEETS OF THE REPLACEMENT OF EQUIPMENT,
 CURBS AND OR ROOF TOP A/C STANDS. HOW WILL CURRENT
 DESIGN LOADS BE DETERMINED? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 7.2. RISK CATEGORY.
  
 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  