| Plan Review Notes For Permit 15090742 |
| Permit Number |
15090742 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-10-06 16:23:16 | ****CORRECTIONS**** | | | | | | ART LANGE - BUILDING INSPECTOR | | | 561-805-6667 [email protected] | | | FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA | | | RESIDENTIAL CODE 2015 5TH EDITION | | | | | | | | | 1. FBC 109.3 BUILDING PERMIT VALUATION. PERMIT VALUE | | | TOO LOW. PROVIDE A NEW PERMIT VALUE FOR THE 30 | | | OPENINGS. FOR PERMITTING PURPOSES, VALUATION OF | | | BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE | | | TO INCLUDE STRUCTURAL, MARKETING COSTS, OVERHEAD AND | | | PROFIT . VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | 2. FBC 1603.4.1, INCLUDE WIND DESIGN CRITERIA. SHOW | | | PRESSURES AT EACH OPENING. | | | | | | 3. SUBMIT 2 COPIES OF THE NOA FOR MULLIONS. |
|